EasyManua.ls Logo

doble SFRA - Sample SFRA Test Results

doble SFRA
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Setting Up and Running a Test
72A-2570-01 Rev. K 07/2011 3-25
Diagnosing Open-Circuit Response
An open-circuit response may be caused by the black test lead dropping off the
bushing, a poor connection, or damage within the test lead. The discrete
change in the lower frequency range in Figure 3.39 on page 3-25 shows
typical open-circuit behavior: about –90 to –100 dB. Investigate a test like this
to see if the open circuit lies in the test setup or the transformer.
Figure 3.39 Typical Open-Circuit Trace
Sample Test Results
This section provides typical results from a number of transformer windings
and designs. These are examples of how designs and phase results vary
between transformers.
Three Responses for One Transformer
Figure 3.40 on page 3-26 shows the two open-circuit responses and the
short-circuit response of one phase of an autotransformer. The three traces are
clearly different at low frequencies.
Typically, the HV response starts at a much lower level than the LV response.
The short-circuit response approaches 0 dB at low frequency but comes back
in line with the HV response at higher frequencies.

Table of Contents

Related product manuals