Sweep Frequency Response Analyzer (SFRA) User Guide
3-28 72A-2570-01 Rev. K 07/2011
Figure 3.43 Short-Circuit Test Trace
Even when responses are shown in magnification (Figure 3.44), they are under
the average divergence of 0.2 dB among phases. This is a useful diagnostic
where no previous results are available.
Figure 3.44 Short Circuit Trace – Detail