6. Select - Protocol → Advanced - Accept.
Figure 81 – Example of Network Menu Setup
7. Once completed, use the power switch on the rear of the instrument to turn the power OFF. Leave
the instrument OFF for 10 seconds before turning the power back ON.
8. Open - Main Menu → Communications Menu → Network Menu.
9. The Start-up Mode automatically changes to Read IP and the current network port settings will be
displayed on the screen.
10. When viewing is complete select - Start-up Mode → Normal - Accept.
4.3.3 Port Forwarding on Remote Modem/Router Setup
When using the network port to connect to the router / modem with NAT enabled, the user will need
to add IP mapping to ensure that data is forwarded through to the desired port. This is known as port
forwarding. To set-up the port for the instrument, the user needs to go into the modem/router
configuration. Normally, the user will see the port forwarding setup under Port Forwarding, NAT, or
Port Mapping menu. Below is an example port forwarding setup .
The default port for the Serinus range of instruments is 32783. The destination address is the
instrument IP address setup in the Network Menu.
Figure 82 – Port Forwarding Example