Operation
Digital Output State
Description
Span
Performing a span check.
Zero
Performing a zero check.
System Fault
Any system fault (the red light is ON).
Maintenance Mode
User has activated maintenance mode.
Over Range AO 0
Over range for the analog output when channel 0 is
active.
Over Range AO 1
Over range for the analog output when channel 1 is
active.
Over Range AO 2
Over range for the analog output when channel 2 is
active.
3.4.29 Network Menu (Option)
Main Menu Communications Menu Network Menu
The Network Menu only appears when the Network Port is enabled in the Hardware Menu (refer to
Section 3.4.34). The Network Menu allows the user to view or set the IP Address, Netmask and
Gateway if the optional network port is installed.
Figure 71 Network Menu Screen
Start-up Mode
The following modes are available:
Normal: In this mode nothing is done with the network port
during boot-up. It is assumed to be configured correctly or
unused.
Read IP: This mode interrogates the network port for its IP
address. The menu will display the network address after
boot-up.
Set IP: The user may enter an IP address, Netmask and
Gateway address (following the usual rules for formatting
these addresses). At this time the instrument does not
validate the correctness of these entries. After a user power
cycle, the instrument will first instruct the network port on its
new address. It will switch to Read IP mode and read back
the address it just set so the user may verify it in the menu.