FloBoss 407 Instruction Manual
Rev 5/00 2-23
5.
Verify the FloBoss performs as required.
6.
If you changed the configuration, save the current configuration data to permanent configuration
memory.
7.
If you changed the configuration or any FSTs, save them to disk. See Section 2.5.2 for more
information on performing these saves.
2.5.4 Warm Start
A warm start temporarily suspends all input/output (I/O) scanning. I/O processes are restarted from
their last calculated values. A warm start clears and restarts all user-enabled flags. A warm start also
starts all FSTs to the first instruction.
NOTE
If your FloBoss is semi-functional, perform the RAM Backup Procedure
before removing power from your FloBoss. Refer to Section 2.5.2, Backup
Procedure Before Removing Power, on page 2-21.
To perform a warm start, remove power from your FloBoss and reapply power.
2.5.5 Cold Start
A cold start reloads all configuration data from electrically erasable read only memory (EEPROM),
clears all history, events, and alarm logs, disables all user program tasks, and disables all user data
types. The RESET switch permits a restart from the boot block of the flash memory (cold hard start)
rather than from RAM (warm start). Hold the RESET switch down during power-up to initiate a cold
hard start; otherwise, the switch has no effect.
NOTE
If your FloBoss is semi-functional, perform the previously described RAM
Backup Procedure before removing power from your FloBoss. Refer to
Section 2.5.2, Backup Procedure Before Removing Power on page 2-21.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FLOBOSS 407 and is the answer not in the manual?

Emerson Fisher FLOBOSS 407 Specifications

General IconGeneral
BrandEmerson
ModelFisher FLOBOSS 407
CategoryControl Unit
LanguageEnglish

Related product manuals