FloBoss 407 Instruction Manual
Rev 5/00 B-15
Press ALT, then CALIBRATE on the keypad. The following sequence begins:
Select Meter Run
TAG 1
TAG ...........
Exit
Calibration Step 1
Push ENTER to go to
Freeze Values Menu
Calibration Step 2
TAG OF METER DATA
DP Reading
Press Reading
Temp Reading
Freeze the Meter
Exit
Calibration Step 3
Select Meter Input
DP Reading
Press Reading
Temp Reading
Exit
Calibration Step 4
DP Reading
Calibrate
Exit
Zero Shift Effect
Verify
Calibration Step 5
Press the ENTER key to select a meter run.
Selecting EXIT returns the date and time
display and exits the calibration program.
Press the ENTER key to advance to the
next display and key in the desired freeze
values.
The program scrolls through a list shown
to the left. After entering desired Freeze
values, press the ENTER key when FREEZE
THE METER displays. The program next
displays SELECT METER INPUT. Selecting
EXIT returns to Calibration Step 1.
The program scrolls through the
following meter input list: DP READING
PRESS READING, TEMP READING, EXIT.
Press the ENTER key to select an input for
calibration. The selected input displays
as shown in Calibration Step 5.
Step 5 is the hub of the calibration
program. The scrolling option list
includes CALIBRATE, ZERO SHIFT EFFECT,
VERIFY, and EXIT. Select the CALIBRATE
option to calibrate the selected input. An
EXIT on this step returns to the previous
step (Step 4) to select another input.