3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
118 Endress+Hauser
System Unit -
Pressure
AUTO - OOS Use this parameter to select the unit for pressure.
The unit you select here is also valid for:
Simulation
Specified pressure
Options:
bar a
bar g
psi a
psi g
Factory setting:
bar g
! Note!
The unit selected here has no influence on the transmitted process variable
to the Analog Input function block.
Low Flow Cut Off -
Assign
AUTO - OOS Use this parameter to assign the switching point for low flow cut off.
Options:
OFF
MASS FLOW
VOLUME FLOW
COR. VOLUME FLOW
Factory setting:
MASS FLOW
Low Flow Cut Off -
On-Value
AUTO - OOS
Use this parameter to assign a value to the switch-on point for low flow cut off.
Low flow cut off is active if the setting is a value not equal to 0.
User input:
5-digit floating-point number
Factory setting:
Depends on nominal diameter and country Page 193 ff.
! Note!
With low flow cut off active, the status condition of the process variable
changes to UNCERTAIN.
Low Flow Cut Off -
Unit
read only Displays the unit of the low flow cut off.
! Note!
Depending on the process variable selected, the unit is taken from the
corresponding parameter "System Unit - Mass Flow", "System Unit - Volume
Flow" or "System Unit - Cor. Volume Flow".
"Flow" Transducer Block / base index 1400:
Parameter
Write access
with operating
mode
(MODE_BLK)
Description

Table of Contents