Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 133
Sys. -
T-DAT Save/Load
AUTO - OOS Use this parameter to save the parameter settings / configuration of the
transmitter in a transmitter DAT (T-DAT), or to load the parameter settings
from the T-DAT into the EEPROM (manual backup function).
Application examples:
After commissioning, the current measuring point parameters can be
saved to the T-DAT as a backup.
If the transmitter is replaced for some reason, the data from the T-DAT
can be loaded into the new transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT into EEPROM)
Factory setting:
CANCEL
! Note!
If the target device has an older software version, the message
"TRANSM. SW–DAT" is displayed during startup. Then only the SAVE
option is available.
•LOAD
This option is only possible:
If the target device has the same software version as, or a more recent
software version than, the source device or
If the T-DAT contains valid data that can be called up.
SAVE This option is always available.
Amp. Device Type read only This parameter is only used for service purposes.
"Diagnosis" Transducer Block/base index 1600
Parameter
Write access
with operating
mode
(MODE_BLK)
Description