3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
132 Endress+Hauser
Sys. - Alarm Delay AUTO - OOS Use this function to define a time span for which the criteria for an error
have to be satisfied without interruption before a fault or notice message is
generated.
Depending on the setting and the type of error, this suppression acts on:
•Display
• Output Blocks (AI Blocks), FOUNDATION Fieldbus interface
User input:
0 to 100 s (in steps of one second)
Factory setting:
0 s
" Caution!
If this parameter is used, fault and notice messages are delayed by the time
corresponding to the setting before being forwarded to the downstream
function blocks or the fieldbus host system.
It is therefore imperative to check in advance in order to make sure whether
a delay of this nature could affect the safety requirements of the process. If
fault and notice messages may not be suppressed, a value of 0 seconds must
be entered here.
Sys. -
Sim. Failsafe Mode
AUTO - OOS Use this parameter to set the Analog Input and Totalizer function blocks
to their defined failsafe modes, in order to check whether they respond
correctly. The failsafe mode of the totalizers is defined via the
"Tot. - Failsafe All" parameter ( → Page 154).
Options:
OFF
ON
Factory setting:
OFF
! Note!
Active simulation mode is relayed to downstream function blocks or higher-
level process control systems by means of the status "UNCERTAIN" of the
output value OUT (AI Block).
Sys. - Reset AUTO - OOS Use this parameter to perform a reset of the measuring system.
Options:
NO
RESTART SYSTEM (restart without interrupting power supply)
ORIGINAL TRANSMITTER DATA
Factory setting:
NO
Sys. -
Operation Time
read only The total operating time since the flowmeter was commissioned appears on
the display (in seconds).
Sys. -
Time Since Reset
read only This parameter is only used for service purposes.
"Diagnosis" Transducer Block/base index 1600
Parameter
Write access
with operating
mode
(MODE_BLK)
Description