Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 137
1 = Main line
2 = Additional line
3 = Info line
A0001253
Main Line -
Assign
AUTO - OOS In this parameter, a value to be displayed is assigned to the main line (top
line in the local display). This value is displayed during normal operation.
Options (standard):
OFF
MASS FLOW
MASS FLOW IN %
VOLUME FLOW
VOLUME FLOW IN %
CORRECTED VOLUME FLOW
CORRECTED VOLUME FLOW IN %
DENSITY
REFERENCE DENSITY
TEMPERATURE
TOTALIZER (1 to 3)
AI (1 to 8) - OUT VALUE
PID - IN VALUE (controlled variable)
PID - CAS IN VALUE (external set point)
PID - OUT VALUE (manipulated variable)
Factory setting:
MASS FLOW
Advanced options with optional software package
CONCENTRATION:
TARGET MASS FLOW
% TARGET MASS FLOW
TARGET VOLUME FLOW
% TARGET VOLUME FLOW
CORRECTED TARGET VOLUME FLOW
CARRIER MASS FLOW
% CARRIER MASS FLOW
CARRIER VOLUME FLOW
% CARRIER VOLUME FLOW
CORRECTED CARRIER VOLUME FLOW
% BLACK LIQUOR
° BAUME
° API
° PLATO
° BALLING
° BRIX