Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 159
System Value -
Perc.Carrier
Volume Flow
read only
! Note!
The option is not active unless one of the following was selected:
• In the "Dens. - Function" parameter ( → Page 160)
– % MASS / % VOLUME
– FLEXIBLE and the % VOLUME 2D or % VOLUME 3D option in the
"Dens. - Mode" parameter ( → Page 163).
In this parameter, the currently measured volume flow of the carrier fluid is
displayed as a % (of the overall mass flow). Carrier fluid = transporting liquid
(e.g. water).
Display:
5-digit floating-point number, including unit and sign
System Unit
Volume Flow
AUTO - OOS Use this parameter to select the unit for displaying the volume.
Options:
Metric → cm
3
; dm
3
; m
3
; ml; l; hl; Ml Mega
US → cc; af; ft
3
; oz f; gal; Kgal; Mgal; bbl (normal fluids); bbl (beer);
bbl (petrochemicals); bbl (filling tanks)
Imperial → gal; Mgal; bbl (beer); bbl (petrochemicals)
Factory setting:
m
3
! Note!
The unit of the totalizers is independent of your choice here. The unit for
each totalizer is selected separately for the totalizer in question.
System Value -
Corr.Carrier
Volume Flow
read only
! Note!
The option is not active unless the % MASS / % VOLUME option was
selected in the "Dens. - Function" parameter ( → Page 160).
Use this parameter to display the currently measured corrected volume flow
of the carrier fluid. Carrier fluid = transporting liquid (e.g. water).
Display:
5-digit floating-point number, including unit and sign
System Value -
Spec.Density
read only Displays the concentration in the unit which was defined in the
"Dens. - Function" parameter ( → Page 160)
Display:
5-digit floating-point number, incl. units
System Value -
Spec.Density Others
read only
! Note!
This option is not available unless FLEXIBLE was selected in the parameter
"Dens. - Function" ( → Page 160).
Displays the concentration in the unit which was defined in the
"Dens. - Mode" parameter ( → Page 163).
Display:
5-digit floating-point number, incl. units
"Calculated Density" Transducer Block/base index 2000
Parameter
Write access
with operating
mode
(MODE_BLK)
Description