3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
162 Endress+Hauser
Dens. -
Sqr.Exp.Coef.Target
AUTO - OOS
! Note!
The option is not active unless one of the following was selected in the
parameter "Dens. - Function" ( → Page 160):
• % MASS / % VOLUME
• %-BLACK LIQUOR
Use this parameter to enter the fluid-specific square expansion coefficient for
the carrier fluid for non linear temperature curves. This value is required for
temperature-compensated calculation of the target fluid content in a
two-phase fluid.
User input:
5-digit floating-point number, including unit and sign
Factory setting:
0.0000 e
–6
[1/K
2
]
Dens. -
Lin.Exp.Coef.
AUTO - OOS
! Note!
The option is not active unless one of the following was selected in the
parameter "Dens. - Function" ( → Page 160):
• ° BAUME < 1 SG
• ° BAUME > 1 SG
•° API
•° PLATO
•° BALLING
• ° BRIX
Use this parameter to enter the fluid-specific linear expansion coefficient
(for linear temperature curves) to calculate the temperature-compensated
density functions.
User input:
5-digit floating-point number, including unit and sign
Factory setting:
0.5000 e
-3
[1/K]
Dens. -
Sqr.Exp.Coef.
AUTO - OOS
! Note!
The option is not active unless one of the following was selected in the
parameter "Dens. - Function"
( → Page 160):
• ° BAUME < 1 SG
• ° BAUME > 1 SG
•° API
•° PLATO
•° BALLING
• ° BRIX
Use this parameter to enter the fluid-specific square expansion coefficient
(for nonlinear temperature curves) to calculate the temperature-
compensated density functions.
User input:
5-digit floating-point number, including unit and sign
Factory setting:
0.0000 e
–6
[1/K
2
]
"Calculated Density" Transducer Block/base index 2000
Parameter
Write access
with operating
mode
(MODE_BLK)
Description