Auxiliary modules
AUXILIARY MODULES
Chokes
4.
Ref.2003
· 145 ·
QC-PDS
HARDWARE
Select the relevant CHOKE according to the table for the installed
regenerative power supply.
Installation
See section, 6.6 CHOKE to carry out a proper installation. See dimensions
in section, 11.9 CHOKES.
T. H4/6
Selecting the
CHOKE
according to the installed regenerative power
supply.
POWER SUPPLY CHOKE
QC-RPS-030-F
CHOKE RPS-45
QC-RPS-160-

CHOKE RPS-160
MANDATORY. A CHOKE must always be installed when there is a
regenerative power supply (regulated) ad always placed between the
power supply and the mains filter (after the - KM1 contactor). The cable
joining the CHOKE to the power supply must never exceed two meters in
length and it needs to be shielded.