Installation
INSTALLATION
Connection of the control and communications signals
8.
Ref.2003
· 299 ·
QC-PDS
HARDWARE
8.6.11 Connections for STO · Safe Torque Off · control signals
Refer to the examples in chapter 9. FUNCTIONAL SAFETY and diagrams in
ANNEXES of chapter 10. CONNECTION DIAGRAMS.
All information regarding the X13, X13A and X13B connectors can be
found in chapter 3. DRIVES.
MANDATORY. ALWAYS
make the connections using:
0.5 mm² cross-sectional conductors using a 10 mm sleeveless ferrule.
Maximum length of the stripped end, 8 mm.
or
0.34 mm² cross-sectional conductors using a 14.5 mm sleeved ferrule
.
Length of ferrule, 10 mm. Maximum length of the stripped end, 12 mm.