Electrical connections
302
Ref.2003
· 254 ·
QC-PDS
HARDWARE
8.5.1 Connecting the main power supply to the mains
With a QC-RPS-030-FX regenerative power supply
Connecting the power input from the three-phase mains via the - KM1
contactor. The main power supply connection to the mains via the MPC-
4x
multi-pole cable between terminals U1/U, V1/V, W1/W of the A19/X11
connector of the power supply and terminals U1, V1, W1 of the RPS-45
CHOKE. The connection between the chassis and the protective earth (PE)
is made via the ground screw located on the upper part of the power supply
and for the CHOKE via its ground terminals. The power cable shield is
connected to the protective earth at both ends via the GP-1 protective earth
bar.
Be sure to strip the power cable to expose the shield at both ends. Use
metal clamps to make these GP-1 connections. Also refer to the connection
diagram on sheet 14 of ANNEX A3.
MANDATORY. Protect the equipment with fuses on the three-phase
supply lines L1, L2 and L3. Follow the indications given in section 6.2
PROTECTION FUSES in this manual.
F. H8/12
QC-RPS-030-F
. Power input from the three-phase mains to the main
regenerative power supply.
U 1 / U
C H O K E
R P S - 4 5
T N - S m a i n s
L 1 L 2 L 3P E
T 1
P E
T 2 T 3
U 1 V 1 W 1
P E
N
G P - 1
A 1 9 / X 1 1
V 1 / V
W 1 / W
G P - 1
A19/X11
Note.
The L1, L2, L3 phases may be
connected in any sequence.
CHOKE
RPS-45
A19/X11
PE connection
QC-RPS-030-F
MPC-4x... cable without
connectors (mm²)
MPC-4x... cable without
connectors (mm²)
PE