Installation
INSTALLATION
Location
8.
Ref.2003
· 239 ·
QC-PDS
HARDWARE
8.1.4 Electrical considerations
Indications regarding EMC
Electromagnetic Compatibility EMC is covered by the following standards:
MANDATORY. The electrical installation should be carried out in
compliance with standard IEC 60204-1.
T. H8/2
Standards regarding Electromagnetic Compatibility.
IEC 61800-3:2017
*note)
Category C3. Variable speed electrical power drive
systems. Part 3: EMC product standard, including
specific testing methods.
IEC 61800-5-2: 2016
Variable speed electrical power drive systems. Part 5-2:
Safety Requirements. Functional.
*note)
MANDATORY. The EMC directive defines equipment as any device
or fixed installation. This device is identified as a fixed installation and is
meant to work inside an electrical cabinet according to category C3 and is
IEC 61800-3 compliant.
*note)
MANDATORY. The installation that includes this product may need
a harmonic suppressing filter to comply with the standard IEC 61800-3
which is harmonized with the EMC Directive. Otherwise, when applying
solutions to limit the harmonics for each QC-PDS system included in the
installation, this could be an expensive solution and/or it might not make
any technical sense. It is better to apply a global solution
MANDATORY. This type of Power Drive System is not designed to be
used with a domestic low-voltage power supply mains. Radio frequency
disturbances may be expected when used in this case. However,
equipment whose compliance with the essential requirements set out in
item 1. General requirements of annex I of the EMC Directive that are not
ensured in residential areas will include an indication with this restriction on
use.