Installation
8.
INSTALLATION
Connection of the control and communications signals
302
Ref.2003
· 298 ·
QC-PDS
HARDWARE
8.6.10 Connections for basic control signals
QC-PS-
power supplies
All information regarding the X14 connector can be found in chapter 2.
POWER SUPPLIES.
Refer to the diagrams in ANNEX A1 and ANNEX A2 of chapter 10. CONNECTION
DIAGRAMS.
QC-RPS-160-SN0 power supplies
All information regarding the X35 connector can be found in chapter 2.
POWER SUPPLIES.
MANDATORY. ALWAYS
make the connections using:
0.5 mm² cross-sectional conductors using a 10 mm sleeveless ferrule.
Maximum length of the stripped end, 8 mm.
or
0.34 mm² cross-sectional conductors using a 14.5 mm sleeved ferrule
.
Length of ferrule, 10 mm. Maximum length of the stripped end, 12 mm.
MANDATORY. ALWAYS make the connections using:
0.5 mm² cross-sectional conductors using a 10 mm sleeveless ferrule.
Maximum length of the stripped end, 8 mm.
or
0.34 mm² cross-sectional conductors using a 14.5 mm sleeved ferrule
.
Length of ferrule, 10 mm. Maximum length of the stripped end, 12 mm.