Power supplies
POWER SUPPLIES
Regenerative Power Supplies
2.
Ref.2003
· 75 ·
QC-PDS
HARDWARE
2.2.6 Indicator lights, push buttons and other elements
For models QC-RPS-
-F
Status leds
LEDs displaying the status of the QC-RPS-
-F
main power supply are
found on the front upper section of the unit. See the figure.
Meaning
D8|D9 leds. Configuration and error status leds:
D10|D11 leds. Status leds for Ethernet and SERCOS-III interface
communication.
Push buttons
Push buttons not provided.
Modes Meaning
OFF
ON
Blinking with t ON at 50%
Blinking with t ON at 80 %
Left (led D8) / right (led D9), alternate blinking
Error
D8 D9 Meaning
Initial state.
Equipment is not
configured.
Equipment configured, SERCOS-
III with no voltage in the DC BUS.
Configured unit,
SERCOS-III with voltage + DC
BUS not enabled.
Configured unit,
SERCOS-III with voltage + DC
BUS not enabled.
Error status
Internal code error.
Miniboot error, non-DSP version.
axis 2 configured
axis 2 not configured
axis 1 configured
axis 2 configured
axis 2 not configured
axis 1 configured
one blink per
sequence
number of blinks
= error group
burst
flickering
INFORMATION.
Display the error codes on the QUERCUS CNC screen.
i
INFORMATION. The D10|D11 LEDs indicate the status of the transmission
between two units using a SERCOS-III connection and must ONLY be
interpreted by the unit connected to B10B.
i
Led Name Status Meaning
D10
LINK
ON Physical connection established
OFF No connection
D11
ACTIVITY
OFF No activity
LIT FIXED
(not blinking)
Establishing SERCOS-III
communication ·active port·
Blinking
2 Hz. Software update procedure or
inactive port.
4 Hz. SERCOS-III communication
established ·active port·

Table of Contents