Installation
INSTALLATION
Mechanical connections
8.
Ref.2003
· 251 ·
QC-PDS
HARDWARE
8.4 Mechanical connections
8.4.1 Plate connection in the power DC BUS
The connection of the modules on the DC BUS are made using two flat
plates to join the under cover (+/-) terminals of the BUS DC of the power
supply with the under cover (+/-) terminals of the BUS DC of the adjacent
QC-DR drive, respectively. See figure.
ALWAYS install step plates and flat plates for any module size|0 in
intermediate positions or place several of them consecutively in the DC
BUS. See figure.
Remember that:
F. H8/10
A17 terminal. Attaching the power DC BUS between the power supply and the
drive.
F. H8/11
A17 terminal. Connection of the power DC BUS between modules size|0,
consecutively or in intermediate positions.
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
QC-BPM-100
QC-APS3-15
QC-RPS-030-FX QC-DR-X-FX QC-DR-X+X-FD2
MANDATORY. The tightening torque to secure the plates to these
connection terminals must be between 2.3 and 2.8 N·m.
WARNING. ALWAYS connect a QC-BPM-100 module next to a QC-RPS-
- regenerative power supply if a controlled stop of the motors is
required in the event of a mains power outage. In the event that this module
is not installed, the motors will be stopped by friction.
MANDATORY. When installing a QC-BPM-100 module to the QC-PDS
system, ensure to connect it to the DC BUS and attach it tightly to the
adjacent module ensuring a proper electrical contact
.