Selection criteria
SELECTING CRITERIA
Selecting the main power supply
5.
· 195 ·
Ref.2003
QC-PDS
HARDWARE
5.5.3 Power supply selecting criteria
1.
The main power supply must be capable of supplying the power required by the set of drives
connected to it.
MANDATORY. Note that motors from the FM9-
-C5C
-
-A family must be matched
to QC-PDS systems with QC-RPS-
-
regenerative power supplies.
T. H5 /18
First selection criterion for the main power supply of the system.
FIRST CRITERIA
The main power supply must be capable of supplying the power required by all the motor-drive
combinations connected to it.
REQUIRED POWER:
1
+
2
=
A
kW
Rated power depending on the S1
duty cycle at the DC BUS
Main power supply
in kW. Reference
NON-REGENERATIVE
POWER SUPPLIES
If A
25 QC-PS-025
If 25 < A
45 QC-PS-045
If A > 45
- Refer to note below -
REGULATED REGENERATIVE
POWER SUPPLIES
If A
30 QC-RPS-030-F
If 30 < A
160 QC-RPS-160-
If A A > 160
- Refer to note below -
If the required rated power (calculated A value) exceeds 160 kW, then install a second main power
supply. Divide the set of drives into two groups so they can be powered by different power supplies.
Refer to the IMPORTANT NOTE below.
IMPORTANT NOTE
. When using two power supplies on the same machine, they must make up two
independent groups with their own drives. Only
the
SERCOS-III BUS
can be common for both
groups.
DANGER.
NEVER
connect the DC BUSES of the main power supplies in parallel.
ALWAYS
install the two groups separately.