WARNING. The resistor should be mounted away from the rest of the
. The connection of ONE external braking resistor with internal
Connect the fan connection terminals to an outlet of
the single-phase 50/60 Hz, 220/240 V AC electrical
cabinet.
Consumption: 0.15/0.13 A, 23/20 W.
Connection terminals on the
external braking resistor
Tk connection terminals of
the internal thermostat
Always install it vertically
R
R
Diagram
Connect one of the two
terminals of the thermostat to
the +24 V DC of an external
power supply in the electrical
cabinet and the other to a PLC
input.
Important. Remember to
manage the chosen PLC input
in the PLC program to generate
an error when exceeding the
limit temperature (160 °C)
detected by the sensor and to
open the contact.
Two FASTON plug-in
male terminals with a tab
size of 2.8 x0.5 mm for
fan connection
Connect the R terminals of the external braking resistor to the X15
connector on the QC-PS-
non-regenerative power supplies.
X15