Installation
INSTALLATION
Electrical connections
8.
Ref.2003
· 273 ·
QC-PDS
HARDWARE
How to install ONE external braking resistor with internal
thermostat and with fan
WARNING. The resistor should be mounted away from the rest of the
modules or even outside the electrical cabinet, always vertically
and away
from cables and other temperature sensitive material.
F. H8/28
QC-PS-
. The connection of ONE external braking resistor with internal
thermostat and with fan.
INTERNAL
THERMOSTAT
Tk
Tk
+ 24 V DC
PLC INPUT
160°C
R
R
AXIAL FAN
50/60 Hz
220/240 V AC
Connect the fan connection terminals to an outlet of
the single-phase 50/60 Hz, 220/240 V AC electrical
cabinet.
Consumption: 0.15/0.13 A, 23/20 W.
Connection terminals on the
external braking resistor
Tk connection terminals of
the internal thermostat
Always install it vertically
R
R
Diagram
Connect one of the two
terminals of the thermostat to
the +24 V DC of an external
power supply in the electrical
cabinet and the other to a PLC
input.
Important. Remember to
manage the chosen PLC input
in the PLC program to generate
an error when exceeding the
limit temperature (160 °C)
detected by the sensor and to
open the contact.
Two FASTON plug-in
male terminals with a tab
size of 2.8 x0.5 mm for
fan connection
Connect the R terminals of the external braking resistor to the X15
connector on the QC-PS-
non-regenerative power supplies.
X15