b codes: Motor 3 Parameters
Drive control
Code Name Data setting range
Change when
running
Data copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Refer
to
page:
b01 Maximum Frequency 3 25.0 to 500.0 Hz N Y *1 Y Y Y Y Y
b02 Base Frequency 3 25.0 to 500.0 Hz N Y 50.0 Y Y Y Y Y
b03 Rated Voltage at Base Frequency 3 0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
N Y2 *1 Y Y Y Y Y
b04 Maximum Output Voltage 3 80 to 240: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500: Output an AVR-controlled voltage
(for 400 V class series)
N Y2 *1 Y Y N N Y
b05 Torque Boost 3 0.0% to 20.0%
(percentage with respect to "b03: Rated Voltage at Base
Frequency 3")
Y Y *3 Y Y N N N
b06 Electric Thermal Overload
Protection for Motor 3
(Select motor characteristics)
1: For a general-purpose motor with shaft-driven cooling
fan
2: For an inverter-driven motor, non-ventilated motor, or
motor with separately powered cooling fan
Y Y 1 Y Y Y Y Y
b07 (Overload detection level) 0.00: Disable
1% to 135% of the rated current (allowable continuous drive
current) of the motor
Y Y1 Y2 *4 Y Y Y Y Y
b08 (Thermal time constant) 0.5 to 75.0 min Y Y *5 Y Y Y Y Y
b09 DC Braking 3
(Braking starting frequency)
0.0 to 60.0 Hz Y Y 0.0 Y Y Y Y N
b10 (Braking level) 0% to 100% (HD mode), 0% to 80% (MD/LD mode) Y Y 0 Y Y Y Y N
b11 (Braking time) 0.00: Disable; 0.01 to 30.00 s Y Y 0.00 Y Y Y Y N
b12 Starting Frequency 3 0.0 to 60.0 Hz Y Y 0.5 Y Y Y Y N
b13 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 3
0: Variable torque load
1: Constant torque load
2: Auto-torque boost
3: Auto-energy saving operation
(Variable torque load during ACC/DEC)
4: Auto-energy saving operation
(Constant torque load during ACC/DEC)
5: Auto-energy saving operation
(Auto-torque boost during ACC/DEC)
N Y 1 Y Y N Y N
b14 Drive Control Selection 3 0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
N Y 0 Y Y Y Y Y
b15 Motor 3 (No. of poles) 2 to 22 poles N Y1 Y2 4 Y Y Y Y Y
b16 (Rated capacity) 0.01 to 1000 kW (when b39 = 0, 2, 3 or 4)
0.01 to 1000 HP (when b39 = 1)
N Y1 Y2 *7 Y Y Y Y Y
b17 (Rated current) 0.00 to 2000 A N Y1 Y2 *7 Y Y Y Y Y
b18 (Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.)
N N 0 Y Y Y Y Y
b20 (No-load current) 0.00 to 2000 A N Y1 Y2 *7 Y Y Y Y Y
b21 (%R1) 0.00% to 50.00% Y Y1 Y2 *7 Y Y Y Y Y
b22 (%X) 0.00% to 50.00% Y Y1 Y2 *7 Y Y Y Y Y
b23 (Slip compensation gain for driving) 0.0% to 200.0% Y* Y 100.0 Y Y Y Y N
b24 (Slip compensation response time) 0.01 to 10.00 s Y Y1 Y2 0.12 Y Y N N N
b25 (Slip compensation gain for braking) 0.0% to 200.0% Y* Y 100.0 Y Y Y Y N
b26 (Rated slip frequency) 0.00 to 15.00 Hz N Y1 Y2 *7 Y Y Y Y N
b27 (Iron loss factor 1) 0.00% to 20.00% Y Y1 Y2 *7 Y Y Y Y Y
b28 (Iron loss factor 2) 0.00% to 20.00% Y Y1 Y2 0.00 Y Y Y Y Y
b29 (Iron loss factor 3) 0.00% to 20.00% Y Y1 Y2 0.00 Y Y Y Y Y
b30 (Magnetic saturation factor 1) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
b31 (Magnetic saturation factor 2) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
b32 (Magnetic saturation factor 3) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
b33 (Magnetic saturation factor 4) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
b34 (Magnetic saturation factor 5) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
*1 The factory default differs depending upon the shipping destination. See Table A.
*3 The factory default differs depending upon the inverter's capacity. See Table B.
*4 The motor rated current is automatically set. See Table C (function code P03).
*5 5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.