5-2
Chap. 5 FUNCTION CODES
Drive control
The FRENIC-MEGA runs under any of the following drive controls. Some function codes apply exclusively to the specific
drive control, which is indicated by letters Y (Applicable) and N (Not applicable) in the "Drive control" column in the
function code tables given on the following pages.
Abbreviation in "Drive control" column
in function code tables
Control target (H18) Drive control (F42)
V/f
V/f control
Dynamic torque vector control
PG V/f
V/f control with speed sensor
Dynamic torque vector control with speed sensor
w/o PG
Vector control without speed sensor
w/ PG
Speed
(Frequency for V/f
and PG V/f)
Vector control with speed sensor
Torque control Torque
Vector control without speed sensor
Vector control with speed sensor
For details about the drive control, refer to "Function code F42 (Drive Control Selection 1)."
The FRENIC-MEGA is a general-purpose inverter whose operation is customized by frequency-
b
asis function codes,
like conventional inverters. Under the speed-
b
asis drive control, however, the control target is a motor speed, not
a
frequency, so convert the frequency to the motor speed according to the following expression.
Motor speed (r/min) = 120 × Frequency (Hz) ÷ Number of poles
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents