v
Conformity to the Low Voltage Directive in the EU
If installed according to the guidelines given below, inverters marked with CE are considered as compliant with the Low
Voltage Directive 2006/95/EC.
Compliance with European Standards
Adjustable speed electrical power drive systems (PDS).
Part 5-1: Safety requirements. Electrical, thermal and energy. EN61800-5-1: 2003
1. The ground terminal G should always be connected to the ground. Do not use only a residual-current-operated
protective device (RCD)/earth leakage circuit breaker (ELCB)* as the sole method of electric shock protection. Be sure
to use ground wires whose size is greater than power supply lines.
*With overcurrent protection.
2. To prevent the risk of hazardous accidents that could be caused by damage of the inverter, install the specified fuses in
the supply side (primary side) according to the following tables.
- Breaking capacity: Min. 10 kA
- Rated voltage: Min. 500 V
Power
supply
voltage
Nominal
applied
motor
(kW)
Inverter type
HD/
LD
mode
Fuse rating
(A)
0.4 FRN0.4G1
-2 10 (IEC60269-1)
0.75 FRN0.75G1
-2 15 (IEC60269-1)
1.5 FRN1.5G1
-2 20 (IEC60269-1)
2.2 FRN2.2G1
-2 30 (IEC60269-1)
3.7 FRN3.7G1
-2
HD
40 (IEC60269-1)
5.5
HD
FRN5.5G1
-2
LD
125 (IEC60269-4)
7.5
HD
FRN7.5G1
-2
LD
160 (IEC60269-4)
11
HD
FRN11G1
-2
LD
160 (IEC60269-4)
15
HD
FRN15G1
-2
LD
200 (IEC60269-4)
18.5
HD
FRN18.5G1
-2
LD
250 (IEC60269-4)
22
HD
FRN22G1
-2
LD
250 (IEC60269-4)
30
HD
FRN30G1
-2
LD
350 (IEC60269-4)
37
HD
FRN37G1
-2
LD
400 (IEC60269-4)
45
HD
FRN45G1
-2
LD
450 (IEC60269-4)
55
HD
FRN55G1
-2
LD
75
HD
FRN75G1
-2
LD
90
HD
Three-phase 200 V
110
FRN90G1
-2
LD
500 (IEC60269-4)
* 4.0 kW for the EU. The inverter type is FRN4.0G1
-4E.
Note: A box (
) in these tables replaces S or E depending on the
enclosure.
A box () in these tables replaces A or E depending on the
shipping destination.
Fuses
Power
supply
voltage
Nominal
applied
motor
(kW)
Inverter type
HD/
MD/LD
mode
Fuse rating
(A)
0.4 FRN0.4G1
-4 3 (IEC60269-1)
0.75 FRN0.75G
-4 6 (IEC60269-1)
1.5 FRN1.5G1
-4 10 (IEC60269-1)
2.2 FRN2.2G1
-4 15 (IEC60269-1)
3.7
(4.0)*
FRN3.7G1
-4A
FRN4.0G1
-4E
HD
20 (IEC60269-1)
5.5
HD
FRN5.5G1
-4
LD
80 (IEC60269-4)
7.5
HD
FRN7.5G1
-4
LD
80 (IEC60269-4)
11
HD
FRN11G1
-4
LD
125 (IEC60269-4)
15
HD
FRN15G1
-4
LD
125 (IEC60269-4)
18.5
HD
FRN18.5G
-4
LD
160 (IEC60269-4)
22
HD
FRN22G1
-4
LD
160 (IEC60269-4)
30
HD
FRN30G1
-4
LD
250 (IEC60269-4)
37
HD
FRN37G1
-4
LD
315 (IEC60269-4)
45
HD
FRN45G1
-4
LD
315 (IEC60269-4)
55
HD
400 (IEC60269-4)
FRN55G1
-4
LD
350 (IEC60269-4)
75
HD
FRN75G1
-4
LD
350 (IEC60269-4)
90
HD
FRN90G1
-4
MD/LD
350 (IEC60269-4)
110
HD
FRN110G
-4
MD/LD
400 (IEC60269-4)
132
HD
FRN132G
-4
MD/LD
450 (IEC60269-4)
160
HD
FRN160G
-4
MD/LD
500 (IEC60269-4)
200
HD
FRN200G
-4
MD/LD
550 (IEC60269-4)
220
HD
250
MD
FRN220G
-4
LD
630 (IEC60269-4)
280
HD
315
MD
355
FRN280G
-4
LD
315
HD
355
MD
400
FRN315G
-4
LD
900 (IEC60269-4)
355
HD
400
MD
450
FRN355G
-4
LD
400
HD
450
MD
FRN400G
-4
LD
1250
(IEC60269-4)
500
HD
FRN500G
-4
LD
630
HD
Three-phase 400 V
710
FRN630G
-4
LD
2000
(IEC60269-4)