8-9
Chap. 8 SPECIFICATIONS
8.3 Common Specifications
Item Explanation
Maximum frequency
25 to 500 Hz (120 Hz for inverters in MD/LD mode)
(120 Hz under vector control without speed sensor)
(200 Hz under V/f control with speed sensor or vector control with speed sensor)
Base frequency 25 to 500 Hz (in conjunction with the maximum frequency)
Starting frequency 0.1 to 60.0 Hz (0.0 Hz under vector control with/without speed sensor)
Setting range
Carrier frequency
0.75 to 16 kHz (HD mode: 0.4 to 55 kW, LD mode: 5.5 to 18.5 kW)
0.75 to 10 kHz (HD mode: 75 to 400 kW, LD mode: 22 to 55 kW)
0.75 to 6 kHz (HD mode: 500 and 630 kW, LD mode: 75 to 500 kW)
0.75 to 4 kHz (LD mode: 630 kW)
0.75 to 2 kHz (MD mode: 90 to 400 kW)
Note: The carrier frequency may automatically drop depending upon the surrounding temperature
or output current to protect the inverter. (The automatic drop function can be disabled.)
Accuracy (Stability)
• Analog setting: ±0.2% of maximum frequency (at 25 ±10°C)
• Keypad setting: ±0.01% of maximum frequency (at -10 to +50°C)
Setting resolution
Analog setting: 1/3000 of maximum frequency (1/1500 for V2 input)
Keypad setting: 0.01 Hz (99.99 Hz or less), 0.1 Hz (100.0 to 500.0 Hz)
Link operation setting: Selectable from the following two types
- 1/20000 of maximum frequency
- 0.01 Hz (fixed)
Speed
control
range
1 : 100 (Minimum speed: Base speed, 4P, 15 to 1500 r/min)
1 : 2 (Constant torque range: Constant output range)
Under V/f
control with
speed sensor
Under dynamic
torque vector
control with
speed sensor
Speed
control
accuracy
• Analog setting: ±0.2% of maximum frequency (at 25 ±10°C)
• Digital setting: ±0.01% of maximum frequency (at -10 to +50°C)
Speed
control
range
1 : 200 (Minimum speed: Base speed, 4P, 7.5 to 1500 r/min)
1 : 2 (Constant torque range: Constant output range)
Under
vector control
without speed
sensor
Speed
control
accuracy
• Analog setting: ±0.5% of base speed (at 25 ±10°C)
• Digital setting: ±0.5% of base speed (at -10 to +50°C)
Speed
control
range
1 : 1500 (Minimum speed: Base speed, 4P, 1 to 1500 r/min, 1024 p/r)
1 : 4 (Constant torque range: Constant output range)
Output frequency
Under
vector control
with speed sensor
Speed
control
accuracy
• Analog setting: ±0.2% of maximum frequency (at 25 ±10°C)
• Digital setting: ±0.01% of maximum frequency (at -10 to +50°C)
Control method
• V/f control
Dynamic torque vector control
V/f control with speed sensor or dynamic torque vector control with speed sensor
Vector control without speed sensor (Not available for MD-mode inverters)
Vector control with speed sensor (with an optional PG interface card mounted)
V/f characteristics
Possible to set output voltage at base frequency and at maximum frequency
AVR control ON/OFF selectable. Non-linear V/f pattern with three arbitrary points.
Torque boost
Auto torque boost (for constant torque load)
Manual torque boost: Desired torque boost (0.0 to 20.0%) can be set.
Select application load with function code F37. (Variable torque load or constant torque load)
Starting torque
22 kW or below: 200% or over, 30 kW or above: 180% or over
Reference frequency: 0.3 Hz with slip compensation and auto torque boost
Start/stop operation
• Keypad (
and keys), external signals (run forward (run reverse) command, etc.),
Communications link (RS-485/fieldbus (option))
• Remote/local operation
Enable input
(Safety stop function)
Opening the circuit between terminals [EN] and [PLC] stops the inverter's output transistor
(coast-to-stop). (Compliant with EN954-1 Cat.3)
Frequency command
• Keypad:
and keys
Analog input (Analog input can be set with external voltage/current input):
0 to ± 10 VDC/0 to ± 100% (terminals [12], [V2])
+4 to +20 mA DC/0 to 100% (terminal [C1])
UP/DOWN operation: Multi-frequency (16 steps), 16-bit parallel
Pulse train input (standard): Pulse input = [X7] terminal,
Rotational direction = One of the digital input terminals
except [X7]
Link operation: Various buses (option)
Reference frequency switching, Remote/local mode switching, Auxiliary frequency setting,
Proportional operation setting, and Inverse operation
Control
Acceleration/
deceleration time
0.00 to 6000 s
Linear/S-curve/curvilinear, Acceleration/deceleration time settings 1 to 4 switchable