5-9
C codes: Control Functions of Frequency
Drive control
Code Name Data setting range
Change when
running
Data copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Refer
to
page:
C01 Jump Frequency 1 0.0 to 500.0 Hz Y Y 0.0 Y Y Y Y N 5-92
C02 2 Y Y 0.0 Y Y Y Y N
C03 3 Y Y 0.0 Y Y Y Y N
C04 (Hysteresis width) 0.0 to 30.0 Hz Y Y 3.0 Y Y Y Y N
C05 Multi-frequency 1 0.00 to 500.00 Hz Y Y 0.00 Y Y Y Y N
C06 2 Y Y 0.00 Y Y Y Y N
C07 3 Y Y 0.00 Y Y Y Y N
C08 4 Y Y 0.00 Y Y Y Y N
C09 5 Y Y 0.00 Y Y Y Y N
C10 6 Y Y 0.00 Y Y Y Y N
C11 7 Y Y 0.00 Y Y Y Y N
C12 8 Y Y 0.00 Y Y Y Y N
C13 9 Y Y 0.00 Y Y Y Y N
C14 10 Y Y 0.00 Y Y Y Y N
C15 11 Y Y 0.00 Y Y Y Y N
C16 12 Y Y 0.00 Y Y Y Y N
C17 13 Y Y 0.00 Y Y Y Y N
C18 14 Y Y 0.00 Y Y Y Y N
C19 15 Y Y 0.00 Y Y Y Y N
C20 Jogging Frequency 0.00 to 500.00 Hz Y Y 0.00 Y Y Y Y N 5-93
C30 Frequency Command 2 0: Enable / keys on the keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12]
and [C1]
5: Voltage input to terminal [V2] (0 to 10 VDC)
7: Terminal command UP/DOWN control
8: Enable
/ keys on the keypad
(balanceless-bumpless switching available)
11: Digital input interface card (option)
12: Pulse train input
N Y 2 Y Y Y Y N 5-29
5-94
C31 Analog Input Adjustment for [12]
(Offset)
-5.0% to 5.0% Y* Y 0.0 Y Y Y Y Y 5-94
C32 (Gain) 0.00% to 200.00% Y* Y 100.00 Y Y Y Y Y
C33 (Filter time constant) 0.00 to 5.00 s Y Y 0.05 Y Y Y Y Y
C34 (Gain base point) 0.00% to 100.00% Y* Y 100.00 Y Y Y Y Y
C35 (Polarity) 0: Bipolar 1: Unipolar N Y 1 Y Y Y Y Y
C36 Analog Input Adjustment for [C1]
(Offset)
-5.0% to 5.0% Y* Y 0.0 Y Y Y Y Y
C37 (Gain) 0.00% to 200.00% Y* Y 100.00 Y Y Y Y Y
C38 (Filter time constant) 0.00 to 5.00s Y Y 0.05 Y Y Y Y Y
C39 (Gain base point) 0.00% to 100.00% Y* Y 100.00 Y Y Y Y Y
C41 Analog Input Adjustment for [V2]
(Offset)
-5.0% to 5.0% Y* Y 0.0 Y Y Y Y Y
C42 (Gain) 0.00% to 200.00% Y* Y 100.00 Y Y Y Y Y
C43 (Filter time constant) 0.00 to 5.00 s Y Y 0.05 Y Y Y Y Y
C44 (Gain base point) 0.00% to 100.00% Y* Y 100.00 Y Y Y Y Y
C45 (Polarity) 0: Bipolar 1: Unipolar N Y 1 Y Y Y Y Y
C50 Bias (Frequency command 1)
(Bias base point)
0.00% to 100.00% Y* Y 0.00 Y Y Y Y Y 5-29
5-95
C51 Bias (PID command 1) (Bias value) -100.00% to 100.00% Y* Y 0.00 Y Y Y Y Y 5-95
C52 (Bias base point) 0.00% to 100.00% Y* Y 0.00 Y Y Y Y Y
C53 Selection of Normal/Inverse
Operation (Frequency command 1)
0: Normal operation
1: Inverse operation
Y Y 0 Y Y Y Y Y 5-67
5-95