EasyManua.ls Logo

Fuji Electric FRENIC-MEGA - E Codes (Extension Terminal Functions); E01 to E07 Terminal (X1) to (X7) Function

Fuji Electric FRENIC-MEGA
287 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-67
5.2.2 E codes (Extension Terminal Functions)
E01 to E07 Terminal [X1] to [X7] Function E98 (Terminal [FWD] Function)
E99 (Terminal [REV] Function)
Function codes E01 to E07, E98 and E99 allow you to assign commands to terminals [X1] to [X7], [FWD], and [REV]
which are general-purpose, programmable, digital input terminals.
These function codes may also switch the logic system between normal and negative to define how the inverter logic
interprets either ON or OFF status of each terminal. The default setting is normal logic system "Active ON." So,
explanations that follow are given in normal logic system "Active ON." The descriptions are, in principle, arranged in
the numerical order of assigned data. However, highly relevant signals are collectively described where one of them
first appears. Refer to the function codes in the "Related function codes" column, if any.
The FRENIC-MEGA runs under V/f control, dynamic torque vector control, V/f control with speed sensor, dynamic
torque vector control with speed sensor, vector control without speed sensor, or vector control with speed sensor. Some
function codes apply exclusively to the specific drive control, which is indicated by letters Y (Applicable) and N (Not
applicable) in the "Drive control" column in the table given below. (Refer to page 5-2.)
Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward"
FWD), stop commands (e.g., "Coast to a stop" BX), and frequency change
commands can be assigned to digital input terminals. Depending upon the assignment states of those terminals,
modifying the function code setting may cause a sudden motor start or an abrupt change in speed.
When the inverter is controlled with the digital input signals, switching run or frequency command sources with
the related terminal commands (e.g.,
SS1, SS2, SS4, SS8, Hz2/Hz1, Hz/PID, IVS, and LE) may cause a sudden
motor start or an abrupt change in speed.
An accident or physical injury may result.
Function code data Drive control
Active ON Active OFF
Terminal commands assigned Symbol
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Related
function codes
0 1000 SS1 Y
Y
Y Y
N
1 1001 SS2 Y
Y
Y Y
N
2 1002 SS4 Y
Y
Y Y
N
3 1003
Select multi-frequency (0 to 15 steps)
SS8 Y
Y
Y Y
N
C05 to C19
4 1004 Select ACC/DEC time (2 steps) RT1 Y
Y
Y Y
N
5 1005 Select ACC/DEC time (4 steps) RT2 Y
Y
Y Y N
F07, F08,
E10 to E15
6 1006 Enable 3-wire operation HLD Y
Y
Y Y
Y
F02
7 1007 Coast to a stop BX Y
Y
Y Y
Y
8 1008 Reset alarm RST Y
Y
Y Y
Y
1009 9 Enable external alarm trip THR Y
Y
Y Y
Y
10 1010 Ready for jogging JOG YYY Y
N
C20,
H54, H55,
d09 to d13
11 1011 Select frequency command 2/1 Hz2/Hz1 Y
Y
Y Y N F01, C30
12 1012 Select motor 2 M2 Y
Y
Y Y Y A42
13 Enable DC braking DCBRK Y
Y
Y Y N F20 to F22
14 1014 Select torque limiter level 2/1 TL2/TL1 Y
Y
Y Y Y
F40, F41,
E16, E17
15 Switch to commercial power (50 Hz) SW50 Y
Y
N N N
16 Switch to commercial power (60 Hz) SW60 Y
Y
N N N
17 1017 UP (Increase output frequency) UP Y
Y
Y Y N
18 1018 DOWN (Decrease output frequency) DOWN Y
Y
Y Y N
Frequency
command:
F01, C30
PID command:
J02
19 1019 Enable data change with keypad WE-KP Y
Y
Y Y Y F00
20 1020 Cancel PID control Hz/PID Y
Y
Y Y N
J01 to J19,
J56 to J62
21 1021 Switch normal/inverse operation IVS Y
Y
Y Y N C53, J01
22 1022 Interlock IL Y
Y
Y Y Y F14
23 1023 Cancel torque control Hz/TRQ N N N N Y H18
24 1024
Enable communications link via RS-485
or fieldbus (option)
LE Y
Y
Y Y
Y
H30, y98
25 1025 Universal DI U-DI Y
Y
Y Y
Y
26 1026
Enable auto search for idling motor
speed at starting
STM Y
Y
Y N
Y
H09, d67
1030 30 Force to stop STOP Y
Y
Y Y
Y
F07, H56