EasyManua.ls Logo

Fuji Electric FRENIC-MEGA - H Codes: High Performance Functions; P Codes: Motor 1 Parameters

Fuji Electric FRENIC-MEGA
287 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-10
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Chap. 5 FUNCTION CODES
P codes: Motor 1 Parameters
Drive control
Code Name Data setting range
Change when
running
Data copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Refer
to
page:
P01 Motor 1 (No. of poles) 2 to 22 poles N Y1 Y2 4 Y Y Y Y Y 5-95
P02 (Rated capacity) 0.01 to 1000 kW (when P99 = 0, 2, 3 or 4)
0.01 to 1000 HP (when P99 = 1)
N Y1 Y2 *7 Y Y Y Y Y 5-96
P03 (Rated current) 0.00 to 2000 A N Y1 Y2 *7 Y Y Y Y Y
P04 (Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip
frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available when
the vector control is enabled.)
N N 0 Y Y Y Y Y
P06 (No-load current) 0.00 to 2000 A N Y1 Y2 *7 Y Y Y Y Y 5-97
P07 (%R1) 0.00% to 50.00% Y Y1 Y2 *7 Y Y Y Y Y
P08 (%X) 0.00% to 50.00% Y Y1 Y2 *7 Y Y Y Y Y
P09 (Slip compensation gain for driving) 0.0% to 200.0% Y* Y 100.0 Y Y Y Y N
P10 (Slip compensation response time) 0.01 to 10.00 s Y Y1 Y2 0.12 Y Y N N N
P11 (Slip compensation gain for braking) 0.0% to 200.0% Y* Y 100.0 Y Y Y Y N
P12 (Rated slip frequency) 0.00 to 15.00 Hz N Y1 Y2 *7 Y Y Y Y N 5-98
P13 (Iron loss factor 1) 0.00% to 20.00% Y Y1 Y2 *7 Y Y Y Y Y
P14 (Iron loss factor 2) 0.00% to 20.00% Y Y1 Y2 0.00 Y Y Y Y Y
P15 (Iron loss factor 3) 0.00% to 20.00% Y Y1 Y2 0.00 Y Y Y Y Y
P16 (Magnetic saturation factor 1) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P17 (Magnetic saturation factor 2) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P18 (Magnetic saturation factor 3) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P19 (Magnetic saturation factor 4) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P20 (Magnetic saturation factor 5) 0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P21 (Magnetic saturation extension
factor "a")
0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P22 (Magnetic saturation extension
factor "b")
0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P23 (Magnetic saturation extension
factor "c")
0.0% to 300.0% Y Y1 Y2 *7 Y Y Y Y Y
P53 (%X correction factor 1) 0% to 300% Y Y1 Y2 100 Y Y Y Y Y
P54 (%X correction factor 2) 0% to 300% Y Y1 Y2 100 Y Y Y Y Y
P55 (Torque current under vector control) 0.00 to 2000 A N Y1 Y2 *7 N N Y Y Y
P56 (Induced voltage factor under
vector control)
50% to 100% N Y1 Y2 85 N N Y Y Y
P57 Reserved *9 0.000 to 20.000 s Y Y1 Y2 *7 - - - - Y
P99 Motor 1 Selection 0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Fuji motors exclusively designed
for vector control)
3: Motor characteristics 3 (Fuji standard motors, 6-series)
4: Other motors
N Y1 Y2 0 Y Y Y Y Y 5-98
H codes: High Performance Functions
Drive control
Code Name Data setting range
Change when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Refer
to
page:
H03 Data Initialization 0: Disable initialization
1: Initialize all function code data to the factory defaults
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
4: Initialize motor 3 parameters
5: Initialize motor 4 parameters
N N 0 Y Y Y Y Y 5-99
H04 Auto-reset
(
Times
)
0: Disable
;
1 to 10 Y Y 0 Y Y Y Y Y
H05
(
Reset interval
)
0.5 to 20.0 s Y Y 5.0 Y Y Y Y Y
H06 Cooling Fan ON/OFF Control 0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
Y Y 0 Y Y Y Y Y 5-100
H07 Acceleration/Deceleration Pattern 0: Linear
1: S-curve (Weak)
2: S-curve (Arbitrary, according to H57 to H60 data)
3: Curvilinear
Y Y 0 Y Y Y Y N 5-38
5-101
H08 Rotational Direction Limitation 0: Disable
1: Enable (Reverse rotation inhibited)
2: Enable (Forward rotation inhibited)
N Y 0 Y Y Y Y N 5-101
The shaded function codes (
) are applicable to the quick setup.
*7 The motor parameters are automatically set, depending upon the inverter's capacity and shipping destination. See Table C.
*9 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents