3-12
Basic key operation
To check the status of the I/O signals, set function code E52 to "2" (Full-menu mode) beforehand.
(1) Turn the inverter ON. It automatically enters Running mode. In that mode, press the
key to switch to Programming
mode. The function selection menu appears.
(2) Use the
and keys to display "I/O Checking" (
$i_o
).
(3) Press the
key to proceed to a list of I/O check items (e.g.
4_00
).
(4) Use the
and keys to display the desired I/O check item, then press the key.
The corresponding I/O check data appears. For the item
4_00
or
4_01
, using the and keys switches the display
method between the segment display (for external signal information in Table 3.12) and hexadecimal display (for I/O signal
status in Table 3.13).
(5) Press the
key to return to the list of I/O check items. Press the key again to return to the menu.
Table 3.11 I/O Check Items
LED monitor
shows:
Item Description
4_00
I/O signals on the control circuit
terminals
Shows the ON/OFF state of the digital I/O terminals. Refer to
"
Displaying control I/O signal terminals" on the next page for
details.
4_01
I/O signals on the control circuit
terminals under communications
control
Shows the ON/OFF state of the digital I/O terminals that received a
command via RS-485 and optional communications. Refer to
"
Displaying control I/O signal terminals" and
"
Displaying control I/O signal terminals under communications
control" on the following pages for details.
4_02
Input voltage on terminal [12] Shows the input voltage on terminal [12] in volts (V).
4_03
Input current on terminal [C1] Shows the input current on terminal [C1] in milliamperes (mA).
4_04
Output voltage on terminal [FM1] Shows the output voltage on terminal [FM1] in volts (V).
4_05
Output voltage on terminal [FM2] Shows the output voltage on terminal [FM2] in volts (V).
4_07
Input voltage on terminal [V2] Shows the input voltage on terminal [V2] in volts (V).
4_08
Output current on terminal [FM1] Shows the output current on terminal [FM1] in milliamperes (mA).
4_09
Output current on terminal [FM2] Shows the output current on terminal [FM2] in milliamperes (mA).
4_10
Option control circuit terminal
(I/O)
Shows the ON/OFF state of the digital I/O terminals on the digital input
and output interface cards (options). Refer to "
Displaying control I/O
signal terminals on options" on page 3-14 for details.
4_11
Terminal [X7] pulse input monitor Shows the pulse rate of the pulse train signal on terminal [X7].
4_15
PG pulse rate
(A/B phase signal from the
reference PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
reference PG.
4_16
PG pulse rate
(Z phase signal from the reference
PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the
reference PG.
4_17
PG pulse rate
(A/B phase signal from the slave
PG)
Shows the pulse rate (p/s) of the A/B phase signal fed back from the
slave PG.
4_18
PG pulse rate
(Z phase signal from the slave PG)
Shows the pulse rate (p/s) of the Z phase signal fed back from the slave
PG.
4_19
(Not used.) ―
4_20
Input voltage on terminal [32]
Shows the input voltage on terminal [32] on the analog interface card
(option) in volts (V).
4_21
Input current on terminal [C2]
Shows the input current on terminal [C2] on the analog interface card
(option) in milliamperes (mA).
4_22
Output voltage on terminal [AO]
Shows the output voltage on terminal [AO] on the analog interface card
(option) in volts (V).
4_23
Output current on terminal [CS]
Shows the output current on terminal [CS] on the analog interface card
(option) in milliamperes (mA).
4_24
Customizable logic timer monitor
Monitors the timer or counter value in the customizable logic
specified by U91.