3-5
Chap. 3 OPERATION USING THE KEYPAD
3.4 Programming Mode
The Programming mode provides you with these functions--setting and checking function code data, monitoring maintenance
information and checking input/output (I/O) signal status. The functions can be easily selected with the menu-driven system.
Table 3.4 lists menus available in Programming mode. The leftmost digit (numerals) of each letter string on the LED monitor
indicates the corresponding menu number and the remaining three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu selected last in Programming mode will be
displayed.
Table 3.4 Menus Available in Programming Mode
Menu # Menu
LED monitor
shows:
Main functions Refer to:
0 "Quick Setup"
*fn:
Displays only basic function codes to customize the inverter operation.
Section
3.4.1
!f__
F codes (Fundamental functions)
!e__
E codes
(Extension terminal functions)
!c__
C codes (Control functions)
!p__
P codes (Motor 1 parameters)
!h__
H codes
(High performance functions)
!a__
A codes (Motor 2 parameters)
!b__
b codes (Motor 3 parameters)
!r__
r codes (Motor 4 parameters)
!j__
J codes (Application functions 1)
!d__
d codes (Application functions 2)
!u__
U codes (Application functions 3)
!y__
y codes (Link functions)
1 "Data Setting"
!o__
o codes (Optional functions) (Note)
Selecting each of these
function codes enables its data
to be displayed/changed.
Section
3.4.2
2 "Data Checking"
"rep
Displays only function codes that have been changed from their
factory defaults. You can refer to or change those function code data.
Section
3.4.3
3
"Drive
Monitoring"
#ope
Displays the running information required for maintenance or test
running.
Section
3.4.4
4 "I/O Checking"
$i_o
Displays external interface information.
Section
3.4.5
5
"Maintenance
Information"
%che
Displays maintenance information including cumulative run time. Section
3.4.6
6
"Alarm
Information"
&al
Displays the recent four alarm codes. You can refer to the running
information at the time when the alarm occurred.
Section
3.4.7
7 "Data Copying"
'cpy
Allows you to read or write function code data, as well as verifying it.
Saving the function code data of the currently running inverter into the
keypad and connecting it to a PC running FRENIC Loader enables
data checking on the PC.
Section
3.4.8
(Note) The o codes are displayed only when the corresponding option is mounted. For details, refer to the Instruction Manual