8-6
8.2.2 Three-phase 400 V class series
HD (High Duty)-mode inverters for heavy load (0.4 to 75 kW)
Item Specifications
Type (FRN_ _ _G1E-4) 0.4 0.75 1.5 2.2
3.7
(4.0)
*1
5.5 7.5 11 15 18.5 22 30 37 45 55 75
Nominal applied motor
(kW)
*2
(Output rating)
0.4 0.75 1.5 2.2
3.7
(4.0)
*1
5.5 7.5 11 15 18.5 22 30 37 45 55 75
Rated capacity (kVA)
*3
1.1 1.9 2.8 4.1 6.8 10 14 18 24 29 34 45 57 69 85 114
Rated voltage (V) *4 Three-phase 380 to 480 V (with AVR function)
Rated current (A) 1.5 2.5 4.0 5.5 9.0 13.5 18.5 24.5 32 39 45 60 75 91 112 150
Output ratings
Overload capability 150%-1 min, 200%-3.0 s
Voltage, frequency 380 to 480 V, 50/60 Hz *5
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*7
0.6 1.2 2.1 3.2 5.2 7.4 10 15 20 25 30 40 48 58 71 96
Torque (%) *8 150% 100% 20% 10 to 15%
Braking transistor Built-in
Built-in braking resistor
Braking time (s)
5 s
Braking
Duty cycle (%ED) 5 3 5 3 2 3 2
EMC filter Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
DC reactor (DCR) *9 Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529) IP20, UL open type IP00, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass (kg) 1.8 2.1 2.7 2.9 3.2 6.8 6.9 6.2 10.5 10.5 11.2 26 27 32 33 42
(90 to 630 kW)
Item Specifications
Type (FRN_ _ _G1E-4) 90 110 132 160 200 220 280 315 355 400 500 630
Nominal applied motor
(kW)
*2
(Output rating)
90 110 132 160 200 220 280 315 355 400 500 630
Rated capacity (kVA)
*3
134 160 192 231 287 316 396 445 495 563 731 891
Rated voltage (V) *4 Three-phase 380 to 480 V (with AVR function)
Rated current (A) 176 210 253 304 377 415 520 585 650 740 960 1170
Output ratings
Overload capability 150%-1 min, 200%-3.0 s
Voltage, frequency
380 to 440 V, 50 Hz
380 to 480 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*6, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*7
114 140 165 199 248 271 347 388 436 489 611 773
Torque (%) *8 10 to 15%
Braking transistor
Built-in braking resistor
Braking time (s)
Braking
Duty cycle (%ED)
EMC filter Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
DC reactor (DCR) *9 Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529) IP00, UL open type
Cooling method Fan cooling
Weight / Mass (kg) 62 64 94 98 129 140 245 245 330 330 530 530
*1 4.0 kW for the EU. The inverter type is FRN4.0G1S-4E.
*2 Fuji 4-pole standard motor
*3 Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
*4 Output voltage cannot exceed the power supply voltage.
*5 380 to 440 V, 50 Hz; 380 to 480 V, 60 Hz
*6
3) -61800 (IEC 67 ×
(V) voltageaverage phase-Three
(V) voltageMin. - (V) voltageMax.
(%) unbalance Voltage
=
If this value is 2 to 3%, use an optional AC reactor (ACR).
*7 Required when a DC reactor (DCR) is used.
*8 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*9 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in LD mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
Note: A box () in the above table replaces A or E depending on the shipping destination.