8-5
Chap. 8 SPECIFICATIONS
8.2 Standard Model 2 (EMC Filter Built-in Type)
8.2.1 Three-phase 200 V class series
HD (High Duty)-mode inverters for heavy load
Item Specifications
Type (FRN_ _ _G1E-2) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Rated capacity (kVA)
*2
1.1 1.9 3.0 4.2 6.8 10 14 18 24 28 34 45 55 68 81 107 131
Rated voltage (V) *3 Three-phase 200 to 240 V (with AVR function)
Three-phase 200 to 230 V
(with AVR function)
Rated current (A) *4 3 5 8 11 18 27 37 49 63 76 90 119 146 180 215 283 346
Output ratings
Overload capability 150%-1 min, 200%-3.0 s
Voltage, frequency 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
0.6 1.2 2.2 3.1 5.2 7.4 10 15 20 25 30 40 48 58 71 98 116
Torque (%) *7 150% 100% 20% 10 to 15%
Braking transistor Built-in
Built-in braking resistor
Braking time (s)
5 s
Braking
Duty cycle (%ED) 5 3 5 3 2 3 2
EMC filter Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.) (EN61800-3:2004)
DC reactor (DCR) *8 Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529) IP20, UL open type IP00, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass (kg) 1.8 2.1 3.0 3.1 3.2 6.7 7.0 6.4 10.9 10.9 11.0 25 32 42 43 62 105
LD (Low Duty)-mode inverters for light load
Item Specifications
Type (FRN_ _ _G1E-2) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90
Nominal applied motor
(kW)
*1
(Output rating)
7.5 11 15 18.5 22 30 37 45 55 75 90 110
Rated capacity (kVA)
*2
11 16 20 25 30 43 55 68 81 107 131 158
Rated voltage (V) *3
Three-phase 200 to 240 V
(with AVR function)
Three-phase 200 to 230 V
(with AVR function)
Rated current (A) *4
31.8
(29)
46.2
(42)
59.4
(55)
74.8
(68)
88
(80)
115
(107)
146 180 215 283 346 415
Output ratings
Overload capability 120%-1 min
Voltage, frequency 200 to 240 V, 50/60 Hz
200 to 220 V, 50 Hz,
200 to 230 V, 60 Hz
Allowable
voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5, Frequency: +5 to -5%
Input power
Required capacity
(with DCR) (kVA)
*6
10 15 20 25 30 40 48 58 71 98 116 143
Torque (%) *7 70% 15% 7 to 12%
Braking transistor Built-in
Built-in braking resistor
Braking time (s)
– 3.7 s 3.4 s
Braking
Duty cycle (%ED) 2.2 1.4
EMC filter
Compliant with EMC Directives, Emission and Immunity: Category C3 (2nd Env.)
(EN61800-3:2004)
DC reactor (DCR) *8
Option
Applicable safety
standards
UL508C, C22.2No.14, EN61800-5-1:2003, EN954-1 Cat.3
Enclosure (IEC60529)
IP20, UL open type IP00, UL open type
Cooling method
Fan cooling
Weight / Mass (kg) 6.7 7.0 6.4 10.9 10.9 11.0 25 32 42 43 62 105
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V for 200 V class series and 440 V for 400 V class series.
*3 Output voltage cannot exceed the power supply voltage.
*4 To use the inverter with the carrier frequency of 3 kHz or more at the surrounding temperature of 40°C or higher, manage the load so that the current
comes to be within the rated ones enclosed in parentheses ( ) in continuous running.
*5
3) -61800 (IEC 67 ×
(V) voltageaverage phase-Three
(V) voltageMin. - (V) voltageMax.
(%) unbalance Voltage
=
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Required when a DC reactor (DCR) is used.
*7 Average braking torque for the motor running alone. (It varies with the efficiency of the motor.)
*8 A DC reactor (DCR) is optionally provided. Note that inverters with a capacity of 55 kW in LD mode and inverters with 75 kW or above in all modes
require a DCR to be connected. Be sure to connect it to those inverters.
Note: A box (
) in the above table replaces A or E depending on the shipping destination.