5-79
Function code data Drive control
Active ON Active OFF
Functions assigned Symbol
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Related
function
codes/signals
(data)
48 1048 Motor 1 selected SWM1 Y Y Y Y Y
49 1049 Motor 2 selected SWM2 Y Y Y Y Y
50 1050 Motor 3 selected SWM3 Y Y Y Y Y
51 1051 Motor 4 selected SWM4 Y Y Y Y Y
A42, b42, r42
52 1052 Running forward FRUN Y Y Y Y Y
53 1053 Running reverse RRUN Y Y Y Y Y
54 1054 In remote operation RMT Y Y Y Y Y
(See Section
4.2.2.)
56 1056 Motor overheat detected by thermistor THM Y Y Y Y Y H26, H27
57 1057 Brake signal BRKS Y Y Y Y N J68 to J72
58 1058 Frequency (speed) detected 3 FDT3 Y Y Y Y Y E32, E54
59 1059 Terminal [C1] wire break C1OFF Y Y Y Y Y
70 1070 Speed valid DNZS N Y Y Y Y F25, F38
71 1071 Speed agreement DSAG N Y Y Y N d21, d22
72 1072 Frequency (speed) arrival signal 3 FAR3 Y Y Y Y N E30
76 1076 PG error detected PG-ERR N Y Y Y N d21 to d23
82 1082 Positioning completion signal PSET N N N Y N J97 to J99
84 1084 Maintenance timer MNT Y Y Y Y Y
H44
, H78,
H79
98 1098 Light alarm L-ALM Y Y Y Y Y H81, H82
99 1099 Alarm output (for any alarm) ALM Y Y Y Y Y
101 1101 Enable circuit failure detected DECF Y Y Y Y Y
102 1102 Enable input OFF EN OFF Y Y Y Y Y
105 1105 Braking transistor broken DBAL Y Y Y Y Y H98
111 1111 Customizable logic output signal 1 CLO1 Y Y Y Y Y
112 1112 Customizable logic output signal 2 CLO2 Y Y Y Y Y
113 1113 Customizable logic output signal 3 CLO3 Y Y Y Y Y
114 1114 Customizable logic output signal 4 CLO4 Y Y Y Y Y
115 1115 Customizable logic output signal 5 CLO5 Y Y Y Y Y
U71 to U75,
U81 to U85
Any negative logic (Active OFF) command cannot be assigned to the functions marked with ""in the
"Active OFF" column.
■ Inverter running -- RUN (Function code data = 0)
Inverter output on --
RUN2 (Function code data = 35)
These output signals tell the external equipment that the inverter is running at a starting frequency or higher.
If assigned in negative logic (Active OFF), these signals can be used to tell the "Inverter being stopped" state.
Output signal Basic function Remarks
RUN
Goes OFF even during DC braking or
dew condensation prevention.
RUN2
These signals come ON when the inverter is running.
Under V/f control:
These signals come ON if the inverter output frequency
exceeds the starting frequency, and go OFF if it drops
below the stop frequency. The
RUN signal can also be
used as a "Speed valid" signal
DNZS.
Comes ON even during DC braking,
pre-exciting, zero speed control, or
dew condensation prevention.
Under vector control, both RUN and RUN2 come ON when zero speed control or servo-lock function is enabled.
Undervoltage detected (Inverter stopped) -- LU (Function code data = 3)
This output signal comes ON when the DC link bus voltage of the inverter drops below the specified undervoltage level,
and it goes OFF when the voltage exceeds the level.
This signal is ON also when the undervoltage protective function is activated so that the motor is in an abnormal stop
state (e.g., tripped).
When this signal is ON, a run command is disabled if given.
Torque polarity detected -- B/D (Function code data = 4)
The inverter issues the driving or braking polarity signal to this digital output judging from the internally calculated
torque or torque command. This signal goes OFF when the detected torque is a driving one, and it goes ON when it is a
braking one.