5-87
E44 LED Monitor (Display when stopped)
E44 specifies whether the specified value (data = 0) or the output value (data = 1) to be displayed on the LED monitor
of the keypad when the inverter is stopped. The monitored item depends on the E48 (LED monitor, Speed monitor
item) setting as shown below.
What to be displayed when the inverter stopped
Data for
E48
Monitored item
E44 = 0 (Specified value) E44 = 1 (Output value)
0
Output frequency 1
(before slip compensation)
Reference frequency
Output frequency 1
(before slip compensation)
1
Output frequency 2
(after slip compensation)
Reference frequency
Output frequency 2
(after slip compensation)
2 Reference frequency Reference frequency Reference frequency
3 Motor speed Reference motor speed Motor speed
4 Load shaft speed Reference load shaft speed Load shaft speed
5 Line speed Reference line speed Line speed
7 Display speed (%) Reference display speed Display Speed
E45 LCD Monitor (Item selection)
E45 specifies the LCD monitor display mode to be applied when the inverter using the multi-function keypad is in
Running mode.
Data for E45 Function
0 Running status, rotational direction and operation guide
1 Bar charts for output frequency, current and calculated torque
Example of display for E45 = 0 (during running)
Example of display for E45 = 1 (during running)
Full-scale values on bar charts
Item displayed Full scale
Output frequency Maximum frequency (F03)
Output current Inverter rated current × 200%
Calculated torque Motor rated torque × 200%