Chap. 5 FUNCTION CODES
E43 LED Monitor (Item selection) E48 (LED Monitor (Speed monitor item))
E43 specifies the running status item to be monitored and displayed on the LED monitor.
Specifying the speed monitor with E43 provides a choice of speed-monitoring formats selectable with E48 (LED
Monitor).
Monitor item
Display
sample on
the LED
monitor
LED indicator
: on, : off
Unit Meaning of displayed value
Function
code data
for E43
Speed monitor
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
0
Output frequency 1
(before slip
compensation)
5*00
Hz A kW Hz Frequency actually being output (E48 = 0)
Output frequency 2
(after slip
compensation)
5*00
Hz A kW Hz Frequency actually being output (E48 = 1)
Reference frequency
5*00
Hz A kW Hz Reference frequency being set (E48 = 2)
Motor speed
1500
Hz
A kW r/min
P01
120
× (Hz)frequency Output
(E48 = 3)
Load shaft
speed
30*0
Hz
A kW r/min Output frequency (Hz) × E50 (E48 = 4)
Line speed
30*0
Hz
A
kW m/min Output frequency (Hz) × E50 (E48 = 5)
Display speed (%)
5*0
Hz A kW %
100
frequency Maximum
frequencyOutput
×
(E48 = 7)
Output current
1"34
Hz
A kW A Current output from the inverter in RMS 3
Output voltage
200u
Hz A kW V Voltage output from the inverter in RMS 4
Calculated torque
50
Hz A kW %
Motor output torque in %
(Calculated value)
8
Input power
1*25
Hz A
kW kW Input power to the inverter 9
PID command
1*0*
Hz A kW - 10
PID feedback amount
)0*
Hz A kW -
PID command/feedback amount
transformed to that of virtual physical
value of the object to be controlled (e.g.
temperature)
Refer to function codes E40 and E41 for
details.
12
PID output
10**
Hz A kW %
PID output in % as the maximum
frequency (F03) being at 100%
14
Load factor
50;
Hz A kW %
Load factor of the motor in % as the rated
output being at 100%
15
Motor output
)85
Hz A
kW kW Motor output in kW 16
Analog input
8"00
Hz A kW -
An analog input to the inverter in a format
suitable for a desired scale.
Refer to function codes E40 and E41 for
details.
17
Torque current
48
Hz A kW %
Torque current command value or
calculated torque current
23
Magnetic flux
command
50
Hz A kW %
Magnetic flux command value
(Available only under vector control)
24
Input watt-hour
10*0
Hz A kW kWh
100
Input watt-hour (kWh)
25