the old inverter’s settings for the primary resistance %R1, leakage reactance %X, no-load current, and rated slip
frequency, and specify those values to the new inverter’s function codes.
Vibration that may occur when the motor's coupling is elastic can be regarded as normal vibration due to the output
voltage pattern applied in tuning. The tuning does not always result in an error; however, run the motor and check its
running state.
4.1.9 Function code basic settings < 4 >
Driving a Fuji VG motor exclusively designed for vector control under the vector control with speed sensor (F42* = 6) requires
configuring the following basic function codes. (Refer to Figure 4.1 on page 4-1.)
For details on how to modify the function code data, see Chapter 3, Section 3.4.2 "Setting up function codes -- Menu #1
"Data Setting" --."
Factory default
Function
code
Name Function code data
FRN_ _ _G1
-2A/4A FRN_ _ _G1-4E
p
99
*
Motor 1 selection
2: Motor characteristics 2
(VG motors)
0: Motor characteristics 0
(Fuji standard motors, 8-series)
p
02
*
Motor 1
(Rated capacity)
Same as that of the applied motor
capacity
Nominal applied motor capacity
h
26
Thermistor (for motor)
(Mode selection)
3: Enable (when NTC thermistor)
Also turn SW5 on the control
printed circuit board to the
PTC/NTC side.
0: Disable
d
14
Feedback input
(Pulse input format)
2: A/B phase with 90 degree phase
shift
2: A/B phase
d
15
Feedback input
(Encoder pulse resolution)
0400 (1024)
0400 (1024)
f
03
*
Maximum frequency 1
200 V class series:
60.0 (Hz)
400 V class series:
50.0 (Hz)
200 V class series:
―
4
00 V class series:
50.0 (Hz)
f
07
Acceleration time 1
(Note)
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
f
08
Deceleration time 1
(Note)
Machinery design values
(Note) For a test-driving of the motor,
increase values so that they are longer
than your machinery design values. If
the specified time is short, the inverter
may not run the motor properly.
22 kW or below: 6.00 (s)
30 kW or above: 20.00 (s)
f
11
*
Electric thermal overload
protection for motor 1
(Overload detection level)
0.00: Disable
Depending upon the inverter capacity
After the above configuration, initialize motor 1 with the function code (H03 = 2). It automatically updates the data of the
function codes F04*, F05*, P01*, P03*, P06* to P23*, P53* to P56*, and H46.
When accessing the function code P02*, take into account that changing the P02* data automatically updates the data
of the function codes F04*, F05*, P03*, P06* to P23*, P53* to P56*, and H46.