Chap. 5 FUNCTION CODES
Function code data Drive control
Active ON Active OFF
Terminal commands assigned Symbol
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Related
function codes
32 1032 Pre-excitation EXITE N N Y Y N H84, H85
33 1033
Reset PID integral and differential
components
PID-RST Y
Y
Y Y N
34 1034 Hold PID integral component PID-HLD Y
Y
Y Y N
J01 to J19,
J56 to J62
35 1035 Select local (keypad) operation LOC Y
Y
Y Y
Y
(See Section
4.2.2.)
36 1036 Select motor 3 M3 Y
Y
Y Y
Y
A42, b42
37 1037 Select motor 4 M4 Y
Y
Y Y
Y
A42, r42
39 Protect motor from dew condensation DWP Y
Y
Y Y
Y
J21
40
Enable integrated sequence to switch to
commercial power (50 Hz)
ISW50 Y
Y
N N N
41
Enable integrated sequence to switch to
commercial power (60 Hz)
ISW60 Y
Y
N N N
J22
47 1047 Servo-lock command LOCK N N N Y N J97 to J99
48
Pulse train input
(available only on terminal [X7])
PIN Y
Y
Y Y
Y
49 1049
Pulse train sign
(available on terminals except [X7])
SIGN Y
Y
Y Y
Y
F01, C30,
d62, d63
70 1070 Cancel constant peripheral speed control Hz/LSC
Y Y Y Y
N
71 1071
Hold the constant peripheral speed
control frequency in the memory
LSC-HLD
Y Y Y Y
N
d41
72 1072
Count the run time of commercial
power-driven motor 1
CRUN-M1 Y
Y
N N
Y
73 1073
Count the run time of commercial
power-driven motor 2
CRUN-M2 Y
Y
N N
Y
74 1074
Count the run time of commercial
power-driven motor 3
CRUN-M3 Y
Y
N N
Y
75 1075
Count the run time of commercial
power-driven motor 4
CRUN-M4 Y
Y
N N
Y
H44, H94
76 1076 Select droop control DROOP Y
Y
Y Y N H28
77 1077 Cancel PG alarm PG-CCL N
Y
N Y Y
80 1080 Cancel customizable logic CLC
Y Y Y Y Y
E01 to E07,
U81 to U85
81 1081 Clear all customizable logic timers CLTC
Y Y Y Y Y
98
Run forward
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
FWD Y Y Y Y Y
99
Run reverse
(Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
REV Y Y Y Y Y
F02
100 No function assigned NONE
Y Y Y Y Y
U81 to U85
Some negative logic (Active OFF) commands cannot be assigned to the functions marked with ""in the
"Active OFF" column.
The "Enable external alarm trip" (data = 1009) and "Force to stop" (data = 1030) are fail-safe terminal
commands. In the case of "Enable external alarm trip," when data = 1009, "Active ON" (alarm is triggere