5-107
H42, H43
H48
Capacitance of DC Link Bus Capacitor, Cumulative Run Time of Cooling Fan
Cumulative Run Time of Capacitors on Printed Circuit Boards
H47 (Initial Capacitance of DC Link Bus Capacitor)
H98 (Protection/Maintenance Function)
Life prediction function
The inverter has the life prediction function for some parts which measures the discharging time or counts the voltage
applied time, etc. The function allows you to monitor the current lifetime state on the LED monitor and judge whether
those parts are approaching the end of their service life.
The life prediction function can also issue early warning signals if the lifetime alarm command
LIFE is assigned to any
of the digital output terminals by any of E20 through E24 and E27.
For details, refer to Chapter 7, "MAINTENANCE AND INSPECTION."
Function
code
Name Description
H42
Capacitance of DC link
bus capacitor
Displays the capacitance of DC link bus capacitor (measured value)
• Start of initial capacitance measuring mode under ordinary operating
conditions (0000)
• Measurement failure (0001)
H43
Cumulative run time of
cooling fan
Displays the cumulative run time of cooling fan in units of ten hours.
• Data setting range: 0 to 9999
H47
Initial capacitance of DC
link bus capacitor
Displays the initial capacitance of DC link bus capacitor (measured
value)
• Start of initial capacitance measuring mode under ordinary operating
conditions (0000)
• Measurement failure (0001)
H48
Cumulative run time of
capacitors on printed
circuit boards
Displays the cumulative run time of capacitor on the printed circuit
board in units of ten hours.
• Data setting range: 0 to 9999
When replacing the cooling fan or capacitors on printed circuit boards, it is necessary to clear or modify the data of the
function codes listed above. For details, refer to the documentation for maintenance.