5-145
Output signals
In a customizable logic, outputs from steps 1 to 10 are issued to SO01 to SO10, respectively.
Those outputs SO01 to SO10 differ in configuration depending upon the connection destination, as listed below. (To
relay those outputs to any function other than the customizable logic, route them via customizable logic outputs CL01
to CL05.)
If the connection destination is: Configuration Function codes
Customizable logic input Select one of the internal step output signals SO01 to SO10
in customizable logic input setting.
U01, U02, etc.
Select one of the internal step output signals SO01 to SO10
to be connected to customizable logic output signals 1 to 5
(
CLO1 to CLO5).
U71 to U75
Input to the inverter's sequence
processor
(e.g., "Select multi-frequency"
SS1,
"Run forward"
FWD)
Select an inverter's sequence processor input function to
which one of the customizable logic output signals 1 to 5
(
CLO1 to CLO5) is to be connected. (Same as in E01)
U81 to U85
Select one of the internal step output signals SO01 to SO10
to be connected to customizable logic output signals 1 to 5
(
CLO1 to CLO5).
U71 to U75
General-purpose digital output
(Y terminals)
To specify a general-purpose digital output function (on Y
terminals) to which one of the customizable logic output
signals 1 to 5 (
CLO1 to CLO5) is to be connected, select
one of
CLO1 to CLO5 by specifying the general-purpose
digital output function on any Y terminal.
E20 to E24, E27
General-purpose digital outputs (on Y terminals) are updated every 5 ms. To securely output a customizable
logic signal via Y terminals, include on- or off-delay timers in the customizable logic. Otherwise, short ON
or OFF signals may not be reflected on those terminals.
Function
code
Name Data setting range
Default
setting
U71
Customizable logic output signal 1
(Output selection)
0
U72
Customizable logic output signal 2
(Output selection)
0
U73
Customizable logic output signal 3
(Output selection)
0
U74
Customizable logic output signal 4
(Output selection)
0
U75
Customizable logic output signal 5
(Output selection)
0: Disable
1: Step 1 output
SO01
2: Step 2 output
SO02
3: Step 3 output
SO03
4: Step 4 output
SO04
5: Step 5 output
SO05
6: Step 6 output
SO06
7: Step 7 output
SO07
8: Step 8 output
SO08
9: Step 9 output
SO09
10: Step 10 output
SO10
0
U81
Customizable logic output signal 1
(Function selection)
100
U82
Customizable logic output signal 2
(Function selection)
100
U83
Customizable logic output signal 3
(Function selection)
100
U84
Customizable logic output signal 4
(Function selection)
100
U85
Customizable logic output signal 5
(Function selection)
0 to 100, 1000 to 1081
Same as data of E98/E99, except the
following.
19 (1019): Enable data change with keypad
(data can be modified)
80 (1080): Cancel customizable logic
100