6-2
Table 6.1 Abnormal States Detectable ("Heavy Alarm" and "Light Alarm" Objects)
Code Name
"Heavy alarm"
objects
"Light alarm"
objects
Remarks
Ref.
page
0c1
,
0c2
,
0c3
Instantaneous overcurrent -- 6-10
ef
Ground fault -- 30 kW or above 6-10
0u1
,
0u2
,
0u3
Overvoltage -- 6-10
lu
Undervoltage -- 6-11
lin
Input phase loss -- 6-11
0pl
Output phase loss -- 6-12
0h1
Heat sink overheat 6-12
0h2
External alarm 6-13
0h3
Inverter internal overheat 6-13
0h4
Motor protection (PTC/NTC thermistor) -- 6-13
dbh
Braking resistor overheat 22 kW or below 6-14
fu5
Fuse blown --
200 V class series
with 75 kW or above,
400 V class series
with 90 kW or above
6-14
pbf
Charger circuit fault --
200 V class series
with 37 kW or above,
400 V class series
with 75 kW or above
6-14
0l1
to
0l4
Overload of motor 1 through 4 6-14
0lu
Inverter overload -- 6-15
05
Overspeed -- 6-15
pg
PG wire break -- 6-16
er1
Memory error -- 6-16
er2
Keypad communications error -- 6-16
er3
CPU error -- 6-17
er4
Option communications error 6-17
er5
Option error 6-17
er6
Operation protection -- 6-17
er7
Tuning error -- 6-17
er8
erp
RS-485 communications error (COM port 1)
RS-485 communications error (COM port 2)
6-18
erf
Data saving error during undervoltage -- 6-18
erh
Hardware error --
200 V class series
with 37 kW or above,
400 V class series
with 45 kW or above
6-19
ere
Speed mismatch or excessive speed deviation 6-19
nrb
NTC wire break error -- 6-20
err
Mock alarm -- 6-20
cof
PID feedback wire break 6-20
dba
Braking transistor broken -- 6-20
ero
Positioning control error -- 6-20
ecf
Enable circuit failure -- 6-21
l-al
Light alarm -- -- --
fal
DC fan locked --
200 V class series
with 45 kW or above,
400 V class series
with 75 kW or above
--
0l
Motor overload early warning -- --
0h
Heat sink overheat early warning -- --
lif
Lifetime alarm -- --
ref
Reference command loss detected -- --
pid
PID alarm -- --
uTl
Low torque output -- --
pTc
PTC thermistor activated -- --
rTe
Inverter life (Motor cumulative run time) -- --
cnT
Inverter life (Number of startups) -- --