5-4
Chap. 5 FUNCTION CODES
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Drive control
Code Name Data setting range
Change when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
Torque
control
Refer
to
page:
F26 Motor Sound (Carrier frequency) 0.75 to 16 kHz (HD-mode inverters with 55 kW or below
and LD-mode ones with 18.5 kW or below
0.75 to 10 kHz (HD-mode inverters with 75 to 400 kW and
LD-mode ones with 22 to 55 kW)
0.75 to 6 kHz (HD-mode inverters with 500 and 630 kW
and LD-mode ones with 75 to 500 kW)
0.75 to 4 kHz (LD-mode inverters with 630 kW)
0.75 to 2 kHz (MD-mode inverters with 90 to 400 kW)
Y Y 2
(Asia)
15
(EU)
Y Y Y Y Y 5-53
F27 (Tone) 0: Level 0 (Inactive)
1: Level 1
2: Level 2
3: Level 3
Y Y 0 Y Y N N Y
F29 Analog Output [FM1]
(Mode selection)
0: Output in voltage (0 to 10 VDC)
1: Output in current (4 to 20 mA DC)
Y Y 0 Y Y Y Y Y 5-54
F30 (Voltage adjustment) 0% to 300% Y* Y 100 Y Y Y Y Y
F31 (Function) Select a function to be monitored from the followings.
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback amount
8: PG feedback value
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration (+)
15: PID command (SV)
16: PID output (MV)
Y Y 0 Y Y Y Y Y
F32 Analog Output [FM2]
(Mode selection)
0: Output in voltage (0 to 10 VDC)
1: Output in current (4 to 20 mA DC)
Y Y 0 Y Y Y Y Y
F34 (Voltage adjustment) 0% to 300% Y* Y 100 Y Y Y Y Y
F35 (Function) Select a function to be monitored from the followings.
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback amount
8: PG feedback value
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration
15: PID command (SV)
16: PID output (MV)
Y Y 0 Y Y Y Y Y
F37 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 1
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy saving
(Variable torque load during ACC/DEC)
4: Auto energy saving
(Constant torque load during ACC/DEC)
5: Auto energy saving
(Auto torque boost during ACC/DEC)
N Y 1 Y Y N Y N 5-55
F38 Stop Frequency (Detection mode) 0: Detected speed 1: Reference speed N Y 0 N N N Y N 5-51
F39 (Holding Time) 0.00 to 10.00 s Y Y 0.00 Y Y Y Y N 5-57
F40 Torque Limiter 1-1 -300% to 300%; 999 (Disable) Y Y 999 Y Y Y Y Y 5-57
F41 1-2 -300% to 300%; 999 (Disable) Y Y 999 Y Y Y Y Y
F42 Drive Control Selection 1 0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
N Y 0 Y Y Y Y Y 5-62
F43 Current Limiter (Mode selection) 0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
Y Y 2
Y Y N N N 5-64
F44 (Level) 20% to 200% (The data is interpreted as the rated output
current of the inverter for 100%.)
Y Y 160 Y Y N N N
F50 Electronic Thermal Overload
Protection for Braking Resistor
(Discharging capability)
0 (Braking resistor built-in type), 1 to 9000 kWs,
OFF (Disable)
Y Y1 Y2 *6 Y Y Y Y Y
F51 (Allowable average loss) 0.001 to 99.99 kW Y Y1 Y2 0.001 Y Y Y Y Y
F52 (Resistance) 0.01 to 999Ω Y Y1 Y2 0.01 Y Y Y Y Y
F80 Switching between HD, MD and LD
drive modes
0: HD (High Duty) mode 1: LD (Low Duty) mode
2: MD (Medium Duty) mode
N Y 0 Y Y Y Y Y 5-66
The shaded function codes (