6-56
Table 6.4.2 Software Specifications
Item Specifications
Data update interval 4 ms
Run command Running forward/reverse alarm reset, X1-X14 commands
Speed
command
16-bit binary data, setting resolution 0.005% (against the highest speed)
Operating, braking, torque limiting, alarm relay output signals, etc.
Oper
ation
Operation state
output
Motor speed, torque current command, etc.
Function code
You can reference and change the 255 functions assigned to the link numbers in the
function code list.
Optional function code o30 - o32 (Displayed on the touch panel when this option is installed)
Protective Function
er4
: Network failure (T-Link error)
* Light alarm: o30 and o31 can be used to control the
er4
alarm.
* Heavy alarm: Momentary alarm
* Light alarm: E.g., Signal noise. If the noise is not frequent, the
er4
alarm can be controlled by o30 and o31 to
continue operation.
* Heavy alarm: Fatal failure such as power down on MICREX, disconnection of communication, and hardware
failure.