6.13 AIO Expansion Card
6-239
Chap. 6
CONTROL OPTIONS
6.13.2.2 Specifications
The built-in variable resistors (VR1 and VR2) of the optional AIO expansion card are adjusted before shipping.
Never touch the variable resistors.
Table 6.13.1 Hardware Specifications
Item Specification
Name AIO Expansion Card
Model OPC-VG1-AIO
No. of points 2 ([Ai3] and [Ai4])
Ground [M] (internally connected to built-in control terminal [M] of the card)
Input
Circuit
Input voltage: 0 to ±10 VDC; resolution: 11 bits (signed)
Input impedance: 10 k
No. of points 2 ([AO4] and [AO5])
Ground [M] (internally connected to built-in control terminal [M] of the card)
Output
Circuit
Output voltage: 0 to ±10 VDC; resolution: 12 bits (signed)
Output impedance: 3 k min.
Power supply
±15 V
Power is supplied through the PCB of the FRENIC-VG. Connect the power supply
harness to CN12 of the FRENIC-VG.
VR1 and VR2 These variable resistors are adjusted before shipping. Never touch them.
Table 6.13.2 Software Specifications
Item Specification
Read cycle 1 ms
Function
allocation
Set with functional codes E51 and E52.
Input data
Input
processing
Bias, gain, filter, increment/decrement limiter, zero-hold, polarity changeover,
offset, and dead zone settings are possible individually.
Refresh cycle 1 ms
Function
allocation
Set with functional codes E72 and E73.
Output data
Output
processing
Bias and gain settings are possible individually. Filter settings for all AO functions
are possible.
(1) Input
Two analog input points ([Ai3] and [Ai4]) can be freely set to the following functions.
The functions are set with functions codes E51 through E52. If the same function is assigned to both
[Ai3] and [Ai4], Ai3 takes precedence. If the same function is assigned to [Ai1] - [Ai4], [Ai1] has
priority.
For the Ai functions, refer to Chapter 4, E49 to E52 (Terminal Ai Function) in the FRENIC-VG User's
Manual (Unit Type / Function Codes Edition).
(2) Output
Two analog output points ([AO4] and [AO5]) can be freely set to the following functions.
The functions are set with functions codes E72 and E73.
For the Ao functions, refer to Chapter 4, E69 and E73 (Terminal Ao Function) in the FRENIC-VG User's
Manual (Unit Type / Function Codes Edition).