6.7 CC-Link Interface Card
6-161
Chap. 6
CONTROL OPTIONS
6.7.5.3 Option dedicated function codes
Reloading the CC-Link card can operate o30 to o32 not only as standard function codes but also as option
dedicated function codes.
Table 6.7.8 Option Dedicated Function Codes
Function code name
No.
Name
Keypad
display
Setting range Description
Light
alarm
If a failure occurs, and remains unsolved even after
the operation continues for the time of the timer
(o31), the motor coasts to stop with
er4
alarm
generated.
0
Heavy
alarm
If a failure occurs, immediate coast to a stop. Then
er4
alarm is generated.
Light
alarm
If a failure occurs, and remains unsolved even after
the operation continues for the time of the timer
(o31), the
er4
alarm is generated after stoppage.
1
Heavy
alarm
If a failure occurs,
er4
alarm is generated after
deceleration to stop.
Light
alarm
If a failure occurs, and remains unsolved even after
the operation continues for the time of the timer
(o31),
er4
is displayed after stoppage (without
alarm relay output). The motor restarts after
returning to communications.
2
Heavy
alarm
If a failure occurs,
er4
alarm is generated after
deceleration to stop.
Light
alarm
When a failure occurs,
er4
alarm is not generated.
o30
Operation when an
error occurs
Note 1
MODE ON ER
3
Heavy
alarm
If a failure occurs,
er4
alarm is generated after
deceleration to stop.
o31
Operation time
when an error
occurs
TIMER TL
0.01 to 0.10
to
20.00s
Timer value for operation continuation time upon light alarm
(enabled with o30=0, 1 ,2)
0
VG7 compatible mode with 1 station occupied (CC-Link
Ver. 1)
1 1 X mode with 1 station occupied (CC-Link Ver. 1)
2 2 X mode with 1 station occupied (CC-Link Ver. 2)
3 4 X mode with 1 station occupied (CC-Link Ver. 2)
o32
Format selection
Note 2
FORMAT SEL
4 8 X mode with 1 station occupied (CC-Link Ver. 2)
Note 1: For details on o30 and o31, refer to 6.7.6 "Protection operation."
Note 2: If the o32 value has been changed, the inverter power must be turned ON again to reflect the change content upon the
operation.