5-36
5.3.2.2 Writing single function codes
Query
1 byte 1 byte 2 bytes 2 bytes 2 bytes
Station No. 06 Function code Write data Error check
Hi Lo
Normal response
1 byte 1 byte 2 bytes 2 bytes 2 bytes
Station No. 06 Function code Write data Error check
Hi Lo
Setting "Query"
Broadcasts can be used if the address is "0". In this case, the broadcast request is processed by all
inverters and no response is returned.
FC = 06
Function codes are 2 bytes in length and composed of an identification code and a number.
For details on identification codes, refer to the table in Section 5.3.2.1. The length of read data fields
is fixed at 2 bytes.
Interpreting "Normal response"
A normal response uses the same frame as a query.