6.4 T-Link Interface Card
6-55
Chap. 6
CONTROL OPTIONS
6.4.2 Model and specifications
6.4.2.1 Inverter type
Model elements: OPC-VG1-TL
Name of equipped inverter VG1 FRENIC-VG
Option name: TL T-Link interface card
Accessories
Spacer x 3
M3 screw x 3
6.4.2.2 Specifications
The system will not operate correctly if the switches (RSW1 and RSW2) on this option are not set properly.
Read the instruction below and set them accordingly.
Be sure to power off the inverter before setting the switches (RSW1 and RSW2) on this option.
Table 6.4.1 Hardware Specifications
Item Specifications
Name T-Link Interface Card
Transmission specifications T-Link slave, I/O transmission
Transmission speed 500 kbps
Number of words occupied
in transmission
Selected by the function code o32 "Transmission format selection"
Total of 16 words (8 words + 8 words): 8 words for MICREX FRENIC-VG and
8 words for FRENIC-VG MICREX
Total of 8 words (4 words + 4 words): 4 words for MICREX FRENIC-VG and
4 words for FRENIC-VG MICREX
Terminal TX+, TX-, SD
Rotary switches
RSW1 and RSW2
Address setting, 99W space
4W+4W: Up to 12 cards can be connected.
8W+8W: Up to 6 cards can be connected.
Rotary switches RSW1, 2
Set the station address using the rotary switches RSW1 and RSW2 on the option board.
Figure 6.4.1
* When two or more cards are used, do not allocate the same station address to multiple stations.
* The factory default is RSW1=0 and RSW2=0 (address = 00).
RSW1 RSW2
RSW1: Upper (x10)
RSW2: Lower (x1)