5-30
5.2.7.2 Option frame
(1) Selecting run command (write)
Request frame (Host J Inverter) ................................ FWD command
SOH 1 2 ENQ f 0 0 0 1 ETX 9 2
ACK response frame (Inverter J Host)
SOH 1 2 ACK f ETX D 2
NAK response frame (Inverter J Host) ..................... Cause of error confirmed to be "M26: Send
error process code"
SOH 1 2 NAK f ETX E 1
(2) Polling torque command value (read)
Request frame (Host J Inverter)
SOH 1 2 ENQ h ETX D 3
ACK response frame (Inverter J Host)...................... 85.00% (2134
H
J 8500d J 85.00)
SOH 1 2 ACK h 2 1 3 4 ETX 9 E
(3) Selecting run command with broadcast (write)
Request frame (Host J Inverter) ................................ REV command
SOH 9 9 ENQ f 0 0 0 2 ETX A 2
Broadcast returns no response.