6.7 CC-Link Interface Card
6-167
Chap. 6
CONTROL OPTIONS
6.7.7 Applicable format list
This option card supports formats shown in Table 6.7.12.
Table 6.7.12 Applicable Format List
Function
code
Name Initial value Setting Description Reference page
0
VG7 compatible mode with 1 station occupied
(CC-Link Ver. 1)
*2
6-6-168
1 1 X mode with 1 station occupied (CC-Link Ver. 1) 6-6-173
2 2 X mode with 1 station occupied (CC-Link Ver. 2) *3 6-6-179
3 4 X mode with 1 station occupied (CC-Link Ver. 2) *3 6-6-180
o32
*1
Format
selection
0
4 8 X mode with 1 station occupied (CC-Link Ver. 2)
*3 6-6-182
*1 If the o32 value has been changed, the inverter power must be turned ON again to reflect the change content upon the operation.
*2 The program used for the FRENIC5000VG7S series is available.
*3 When 2 X, 4 X, or 8 X mode of CC-Link Ver. 2 is used, station information at the master station must also be set to 2 X, 4 X, or
8 X, respectively.