EasyManua.ls Logo

Fuji Electric FRENIC-VG Series - Link Function; Link Command Permission Selection

Fuji Electric FRENIC-VG Series
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.7 CC-Link Interface Card
6-185
Chap. 6
CONTROL OPTIONS
6.7.13 Link function
The availability (REM/LOC/COM) of the command data (S area) is switched by function code H30 "Link
operation" and X function "24: link operation selection [LE]". Be familiar with this together with the
control block (refer to Chapter 4).
Writing the standard function codes (F, E, C, P, H, A, o, U, and Lfrom a link is controlled by function
code H29 "link function code protection" and X function "23: link edition permission command
[WE-LK]". Be familiar with this together with the control block (refer to Chapter 4).
6.7.13.1 Link command permission selection
Performing the operation of the inverter via CC-Link requires switching of the mode to the link command
permission mode to select a command (other than 0) via communications by function code H30 "Link
operation". (The system configuration is so flexible that switching a value selected for "link operation",
for example, can select an operation command on the terminal block and a speed command through
communications).
Table 6.7.34
Condition Mode
Command code FB
H
(Operation
mode) = 0
Link command permission
mode
Not assigned
(Factory default)
Command code FB
H
(Operation
mode) = 1.2
Link command no permission
mode
When applicable terminal X is ON Link command permission
mode
Assignment status of 24: link
operation selection [LE] to function
codes E01 to E13 "X function
selection"
Assigned
When applicable terminal X is OFF Link command no permission
mode
Table 6.7.35
Link command permission mode Link command no permission mode
H30 setting
Command data
(S01 to S05, S08 to S17)
Operation command
(S06)
Command data
(S01 to S05, S08 to S17)
Operation command
(S06)
0 × × ×
1 × ×
2 × ×
3 ×
O: Command enabled via communications, X: Command disabled via communications (operated by the command from terminal
block or keypad)
Note 1: S code (command data/operation data) can be written even in the link command no permission status.
Note 2: Writing data into function code S08 "Acceleration time"/S09 "Deceleration time" is independent of link command
permission mode and function code H30 "link operation". The data is always overwritten into function code F07/F08
"acceleration/deceleration time".

Table of Contents

Related product manuals