6-184
Address Signal name Description Remarks
RWwn+10 Response code 2 Turning the RYnF ON stores the response code (Table 6.7.26)
corresponding to the command code specified in RWwn+10,
12, 14, 16, and 18. If the command code has normally been
executed, zero (0) is automatically written; if any error has
occurred during processing of the command code, any value
other than zero is written.
Enabled with 8X setting
RWwn+11 Read data 2 If the command code specified in RWw10, 12, 14, 16, or 18 has
normally been executed, the response data for that command
code is automatically written.
RWwn+12 Response code 3 Same as command code 2
RWwn+13 Read data 3 Same as write data 2
RWwn+14 Response code 4 Same as command code 2
RWwn+15 Read data 4 Same as write data 2
RWwn+16 Response code 5 Same as command code 2
RWwn+17 Read data 5 Same as write data 2
RWwn+18 Response code 6 Same as command code 2
RWwn+19 Read data 6 Same as write data 2
RWwn+1A
|
RWwn+1F
Not used. -
n: Value determined by a station address