6-184 
Address Signal name  Description  Remarks 
RWwn+10  Response code 2  Turning the RYnF ON stores the response code (Table 6.7.26) 
corresponding to the command code specified in RWwn+10, 
12, 14, 16, and 18. If the command code has normally been 
executed, zero (0) is automatically written; if any error has 
occurred during processing of the command code, any value 
other than zero is written. 
Enabled with 8X setting 
RWwn+11  Read data 2  If the command code specified in RWw10, 12, 14, 16, or 18 has 
normally been executed, the response data for that command 
code is automatically written. 
 
RWwn+12  Response code 3  Same as command code 2   
RWwn+13  Read data 3  Same as write data 2   
RWwn+14  Response code 4  Same as command code 2   
RWwn+15  Read data 4  Same as write data 2   
RWwn+16  Response code 5  Same as command code 2   
RWwn+17  Read data 5  Same as write data 2   
RWwn+18  Response code 6  Same as command code 2   
RWwn+19  Read data 6  Same as write data 2   
RWwn+1A 
  | 
RWwn+1F 
Not used.  -   
 